Tytuł:
Thermographic and Electrical Test of Medium Voltage Surge Arresters
Autorzy:
Lisowska-Lis, Agnieszka
Powiązania:
https://bibliotekanauki.pl/articles/114064.pdf
Data publikacji:
2019
Wydawca:
Stowarzyszenie Inżynierów i Techników Mechaników Polskich
Tematy:
surge arresters
medium voltage
thermography
discharge current
cooling
Opis:
The paper presents the results of a thermal test (conducted with thermographic camera, coupled with an electrical test) of medium voltage metal–oxide surge arresters. Surge arresters (for Uc=18 kV) were tested for the leakage current and surface temperature: for 5 minutes under state 50 Hz alternating voltage 18 kV. The surface temperature of the MOAs correlates with an increase in leakage current. The result shows that the 0.6 mA AC leakage current in the medium voltage metal–oxide surge arrester (18 kV) is above the stable operating point, and the loss of electrical power is higher than the effective heat dissipation in the arrester. After 5 minutes of high voltage impact U = 18 kV, the surface temperature of the surge arrester was (4.32±0.55) K higher than the initial temperature. The IR camera can be used to detect the faults of ZnO metal–oxide surge arresters that lead to an increase in surface temperature.
Źródło:
Measurement Automation Monitoring; 2019, 65, 2; 60-63
2450-2855
Pojawia się w:
Measurement Automation Monitoring
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Degradation Processes in Shield-Centring Elements of Surge Arresters
Autorzy:
Papliński, P.
Śmietanka, H.
Ranachowski, P.
Ranachowski, Zbigniew
Wieczorek, K.
Kudela, S. jr.
Powiązania:
https://bibliotekanauki.pl/articles/2203744.pdf
Data publikacji:
2023
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
surge arrester
TSE glass textolite
discharge current
EDS method
Opis:
This paper presents the results of testing samples of shield-centering elements from medium-voltage surge arresters. The elements were made of TSE glass textolite. The elements have been dismantled from different operated surge arresters, which were subjected to discharge currents (short-circuit currents) of different intensity and duration. The discharge currents led to degradation of the tested elements with various degrees of advancement. The degradation was investigated using microscopic methods and energy-dispersive X-ray spectroscopy (EDS). Changes in the content of elements of the surface of textolite materials - as the degradation progresses - were documented. It was found that high discharge current flows resulted in melting of the organic binder, epoxy resin, especially its surface layer. Partial charring and even burning of the resin was noticeable. Furthermore, it was found that with increasing degradation on the surface of the TSE laminate, the carbon and oxygen content, which are part of the organic resin, decreases. Simultaneously the amount of silicon, calcium and aluminium, which are present in the glass fibres, increases. The charring effect of the resin and the formation of conductive paths result in a decrease in the performance of surge arresters and their subsequent failure.
Źródło:
Archives of Metallurgy and Materials; 2023, 68, 1; 237--242
1733-3490
Pojawia się w:
Archives of Metallurgy and Materials
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Metody diagnostyczne ograniczników przepięć
Diagnostics methods of metal oxide surge arresters
Autorzy:
Chrzan, K.
Powiązania:
https://bibliotekanauki.pl/articles/157473.pdf
Data publikacji:
2003
Wydawca:
Stowarzyszenie Inżynierów i Techników Mechaników Polskich
Tematy:
metody diagnostyczne
ograniczniki przepięć
diagnostic methods
metal oxide surge arresters
Opis:
Opisano najważniejsze metody diagnostyczne ograniczników przepięć: pomiaru temperatury sondami TINYTALK lub SAW, kompensacji, pomiaru prądu całkowitego, harmonicznych prądu i składowej rezystancyjnej prądu.
The most important diagnostic methods of metal oxide surge arresters were described: temperature measurement using TINYTALK sensors or SAW sensors (Surface Acoustic Wave), compensation method, total current measurement, current harmonics measurement and resistive current measurement.
Źródło:
Pomiary Automatyka Kontrola; 2003, R. 49, nr 4, 4; 14-16
0032-4140
Pojawia się w:
Pomiary Automatyka Kontrola
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Zagrożenie pożarowe oraz porażeniowe pochodzące od ograniczników przepięć SPD = Fire and shock hazard from SPD surge arresters
Fire and shock hazard from SPD surge arresters
Autorzy:
Wiatr, Julian.
Powiązania:
Zeszyty Naukowe SGSP 2017, nr 63, s. 59-71
Współwytwórcy:
Jaskółowski, Waldemar. Autor
Data publikacji:
2017
Tematy:
Bezpieczniki
Instalacje elektryczne
Ochrona przeciwpożarowa
Pożar
Przepięcie
Rażenie prądem elektrycznym
Artykuł z czasopisma naukowego
Opis:
Bibliografia na stronie 71.
Dostawca treści:
Bibliografia CBW
Artykuł
Tytuł:
Diagnostyka niskonapięciowych warystorowych ograniczników przepięć
Diagnostics of low voltage surge arresters
Autorzy:
Olesz, M.
Powiązania:
https://bibliotekanauki.pl/articles/268637.pdf
Data publikacji:
2012
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
ograniczniki przepięć niskiego napięcia
warystory ZnO
diagnostyka
low voltage ZnO arresters
diagnostics
Opis:
W referacie przedstawiono stosowane w praktyce metody oceny stanu ograniczników przepięć niskiego napięcia (nn). Zestawiono wyniki pomiarów, które umożliwiły określenie stanu technicznego nowych i eksploatowanych ograniczników niskiego napięcia w zakresie charakterystyki przedprzebiciowej.
The paper presents some practical methods of technical state of low voltage ZnO surge arresters evaluation. Several methods of laboratory diagnostics and on - site checks were described. The analysis of commonly applied diagnostic methods was supplied by the results of leakage current measurements for new and degradated in exploitation low voltage arresters.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2012, 31; 113-116
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Comparative Studies on Degradation of Varistors Subjected to Operation in Surge Arresters and Surge Arrester Counters
Autorzy:
Papliński, P.
Wańkowicz, J.
Śmietanka, H.
Ranachowski, P.
Ranachowski, Z.
Kudela, S. jr.
Aleksiejuk, M.
Powiązania:
https://bibliotekanauki.pl/articles/351611.pdf
Data publikacji:
2020
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
surge arrester
surge arrester counter
MO varistor
microstructure of ceramics
ceramic material degradation
Opis:
The paper presents results of investigation of microstructure and micro-hardness for material of ZnO varistors applied to 110 kV surge arrester and surge arrester counter. The research combined two pairs of varistors, each consisted of one varistor subjected before to operation, while the other one was brand new unit and constituted a reference. All varistors were made of the same material by the reputable manufacture. The tests revealed a different degree of the material degradation for varistors subjected before to operation. This also refers to different degradation mechanism observed for the material of these varistors, if typical effects of degradation of aged ZnO varistors were considered as a reference. Physical state of spinel in the microstructure had a significant impact on the material degradation, however a considerable loosening of the microstructure associated with bismuth oxide was observed too. It was surprising, since the precipitates of the bismuth oxide phase most often showed very good binding to the ZnO matrix and high resistance to associated electrical, thermal and mechanical effects. The degradation effects in the ZnO matrix proved to be limited only.
Źródło:
Archives of Metallurgy and Materials; 2020, 65, 1; 367-374
1733-3490
Pojawia się w:
Archives of Metallurgy and Materials
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Microstructure and Degree of Degradation of ZnO Varistors in Surge Arresters Due to Operation
Autorzy:
Papliński, P.
Wańkowicz, J.
Ranachowski, P.
Ranachowski, Z.
Powiązania:
https://bibliotekanauki.pl/articles/356415.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
surge arrester
MO varistor
microstructure of ceramics
ceramic material degradation
Opis:
The paper presents the test results for the microstructure of ZnO varistors comprising high voltage gapless surge arresters. The tests were performed on varistors produced in different periods and by various manufacturers. The research was inspired by different characteristics of changes in values of current flowing through surge arresters as a function of changes in values of system voltage in a 220 kV substation, and the temperature in a multi-year cycle. Furthermore, the effects of varistor microstructure degradation following a failure of an unsealed surge arrester were investigated. The results provided the grounds for assessment of ZnO varistor microstructure parameters in terms of their durability and resistance to degradation processes.
Źródło:
Archives of Metallurgy and Materials; 2018, 63, 3; 1267-1273
1733-3490
Pojawia się w:
Archives of Metallurgy and Materials
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Zagrożenie pożarowe oraz porażeniowe pochodzące od ograniczników przepięć SPD
Fire and shock hazard from SPD surge arresters
Autorzy:
Wiatr, J.
Jaskółowski, W.
Powiązania:
https://bibliotekanauki.pl/articles/136564.pdf
Data publikacji:
2017
Wydawca:
Szkoła Główna Służby Pożarniczej
Tematy:
ogranicznik przepięć SPD
zagrożenie pożarowe
instalacje elektroenergetyczne
pożar
surge arrester SPD
fire hazard
electrical installations
fire
Opis:
Bezpieczeństwo pożarowe jest jednym z najważniejszych wymagań stawianych współczesnym budynkom. Wiąże się z nim szereg wymagań technicznych, które należy spełnić na etapie projektowania. O poziomie bezpieczeństwa pożarowego decyduje m.in. jakość materiałów budowlanych, a także jakość i poziom zabezpieczenia instalacji elektroenergetycznej. Ograniczniki przepięć odgrywają istotną rolę w instalacjach elektroenergetycznych. Ich zadaniem jest ochrona przed przepięciami w urządzeniach elektrycznych i elektronicznych. Mogą one stwarzać zagrożenie pożarowe lub wybuchowe wskutek przepływu prądu następczego pojawiającego się bezpośrednio po wystąpieniu przepięcia. Tak sytuacja będzie miała miejsce, gdy nieprawidłowo zostanie dobrane zabezpieczenie poprzedzające lub/i ogranicznik zostanie przyłączony do głównego toru zasilającego przewodem o zbyt małym przekroju. W artykule autorzy prezentują charakterystykę dwóch stosowanych ograniczników: iskiernikowych i warystorowych, a także wytyczne do ich prawidłowego doboru.
Appropriate level of fire safety is one of the most important requirements for present-day buildings. There are plenty of technical conditions to be fulfilled during the design stage. Among factors influencing fire safety, the following should be mentioned: the quality of construction materials, but also the quality and level of electric installation protection. Lightning arresters play a significant role in the electric installation protection concept. Their role is to protect both electrical and electronic devices from too high voltage. On the other had, they might pose fire and explosion danger, as high current will flow through the arrester immediately after the overvoltage. This situation will take place, if the arrester circuit has been inappropriately designed by using not proper devices, or using wires of too low cross section, especially if the arrester was connected to main power supply. The article presents the characteristics of two commonly used lightning arresters: varistor-based and spark gap, as well as the guidelines of their appropriate design.
Źródło:
Zeszyty Naukowe SGSP / Szkoła Główna Służby Pożarniczej; 2017, 3, 63; 59-71
0239-5223
Pojawia się w:
Zeszyty Naukowe SGSP / Szkoła Główna Służby Pożarniczej
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Badania z zakresu ochrony odgromowej wykonane na Politechnice Wrocławskiej
Lightning protection research carried out at Wroclaw university of technology
Autorzy:
Chrzan, K.L.
Powiązania:
https://bibliotekanauki.pl/articles/267395.pdf
Data publikacji:
2008
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
zwody aktywne
ogranicznik przepięć
gapped surge arresters
metal oxide surge arresters
early streamer emission terminals
Opis:
Wymieniono pierwsze instalacje piorunochronów w Rzeczypospolitej i na Dolnym Śląsku. Opisano badania skuteczności zwodów pionowych na makiecie obserwatorium meteorologicznego oraz skuteczności zwodów aktywnych ESE. Przedstawiono najważniejsze osiągnięcia w zakresie badania odporności zabrudzeniowej odgromników zaworowych i ograniczników beziskiernikowych. Streszczono pomiary wytrzymałości udarowej zabrudzonych izolatorów.
The first installation of Franklin rods in Kingdom of Poland and in Silesia Province were listed. The investigation of Franklin rods efficacy and inefficacy of early streamer emission terminals were shown. The most important achievements in the research of pollution resistance of gapped and gapless surge arresters was reported. The measurements of lightning flashover voltage of polluted insulators were described.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2008, 24; 29-34
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Badania odporności ograniczników przepięć stosowanych w kolejowych układach elektronicznych
Research immunity of surge arresters used in railway electronic systems
Autorzy:
Białek, K.
Powiązania:
https://bibliotekanauki.pl/articles/310247.pdf
Data publikacji:
2018
Wydawca:
Instytut Naukowo-Wydawniczy "SPATIUM"
Tematy:
kompatybilność elektromagnetyczna
odporność
udary
ograniczniki przepięć
electromagnetic compatibility
immunity
surges
surge arresters
Opis:
W artykule przedstawiono badanie odporności na udary elektryczne wybranych dwóch ograniczników przepięć stosowanych w kolejowych układach elektronicznych. Przedstawiono metodykę pomiarową, stanowisko laboratoryjne wg normy PN-EN 61000-4-5 oraz dopuszczalne poziomy narażeń zawarte w normie kolejowej PN-EN 50121-3-2. W artykule zaprezentowano przykładowe wyniki badań oraz przeprowadzono ocenę otrzymanych wyników według obowiązujących unormowań.
The article presents the test of immunity to electric surges of two surge arresters used in railway electronic systems. Metering methodology, laboratory stand according to PN-EN 61000-4-5 and exposure levels included in the railway standard PN-EN 50121-3-2 are presented. The article presents examples of research results and an evaluation of the obtained results according to the applicable regulations.
Źródło:
Autobusy : technika, eksploatacja, systemy transportowe; 2018, 19, 12; 308-311
1509-5878
2450-7725
Pojawia się w:
Autobusy : technika, eksploatacja, systemy transportowe
Dostawca treści:
Biblioteka Nauki
Artykuł

Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies