The paper presents the test results for the microstructure of ZnO varistors comprising high voltage gapless surge arresters. The tests were performed on varistors produced in different periods and by various manufacturers. The research was inspired by
different characteristics of changes in values of current flowing through surge arresters as a function of changes in values of system voltage in a 220 kV substation, and the temperature in a multi-year cycle. Furthermore, the effects of varistor microstructure degradation following a failure of an unsealed surge arrester were investigated. The results provided the grounds for assessment of ZnO varistor microstructure parameters in terms of their durability and resistance to degradation processes.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies