Tytuł:
Evaluation of the Technical Condition of the Active Part of the High Power Transformer Based on Measurements and Analysis of Vibroacoustic Signals
Autorzy:
Borucki, S.
Cichoń, A.
Majchrzak, H.
Zmarzły, D.
Powiązania:
https://bibliotekanauki.pl/articles/176397.pdf
Data publikacji:
2017
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
vibration
vibroacoustic method
core
power transformer
transformer diagnostics
Opis:
This article presents the results of research connected with the development and industrial use of vibroacoustic methods for the evaluation of the technical condition of the active part of transformers. The article presents the results of the analysis of vibrations generated by the high power transformer in which a defect was found on the basis of tests of oil carried out using the chromatography tests. In order to confirm the damage of the active part of this transformer, vibroacoustic measurements were performed in three states of its operation. The measurement using the classical vibroacoustic method included the registration of vibrations at the idle speed and during the load operation of the transformer. The original diagnostic method, so-called the modified vibroacoustic method, was also used during the measurement. The analysis of signals recorded using the classical vibroacoustic method was carried out in the frequency domain by indicating the amplitude of even harmonic vibrations. However, the analysis of signals measured during the commissioning of the transformer was conducted in the time-frequency domain using the short-time Fourier transform (STFT), continuous wavelet transform (CWT), and discrete wavelet transform (DWT). On the basis of the analysis of the results obtained it was stated that the increased level of vibrations of this transformer is a consequence of the loss of rigidity of the mechanical structure of its core.
Źródło:
Archives of Acoustics; 2017, 42, 2; 313-320
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Technical Possibilities of Reducing the Sound Pressure Level Emitted into the Environment by a Power Transformer
Autorzy:
Borucki, S.
Boczar, T.
Cichoń, A.
Powiązania:
https://bibliotekanauki.pl/articles/177473.pdf
Data publikacji:
2011
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
power transformer
corrected sound pressure level
noise
modernization
Opis:
The subject presented in this paper refers to measurements and assessment of the corrected sound pressure level values (noise) occurring around a medium-power transformer. The paper presents the values of noise accompanying the operation of the power object before and after its modernization, which consisted in repeated core pressing and replacement of the cooling system. The main aim of the research work was the assessment of the influence of the repair work on the noise level emitted into the environment.
Źródło:
Archives of Acoustics; 2011, 36, 1; 49-56
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
High-energy transformer’s safety
Monitorowanie temperatury transformatora wysokoenergetycznego z wykorzystaniem czujnika światłowodowego
Autorzy:
Kulig, Magdalena
Powiązania:
https://bibliotekanauki.pl/articles/1203880.pdf
Data publikacji:
2019
Wydawca:
Politechnika Rzeszowska im. Ignacego Łukasiewicza. Oficyna Wydawnicza
Tematy:
transformator mocy
uszkodzenie uzwojenia
blackout
power transformer
winding failure
Opis:
Based on many advantages of fiber optic sensor technology, the article presents the possibility of measuring temperature in difficult environmental conditions, for example in a high electromagnetic field. Fabry-Perot interferometers with a short resonant cavity of low resolution are used in these fiber-optic sensors. The advantages of such a solution include simple and compact construction, low price, low temperature effect and no interference loss due to polarization. Due to the potential of transformer loads, electrical power plants and operating companies test power transformers to assess their condition, set a schedule for maintenance work and plan replacement. Oil temperature measurement is most commonly used using typical sensors. However, this measurement does not reflect the temperature of the winding during the sudden increase in the transformer load. The proposed method of verifying the parameter, which is the winding temperature, can be very attractive for electricity distributors.
Bazując na wielu zaletach technologii czujników światłowodowych, artykuł przedstawia możliwość pomiaru temperatury w trudnych warunkach środowiskowych, na przykład w wysokim polu elektromagnetycznym. W omawianych czujnikach światłowodowych stosuje się interferometry Fabry-Perota, z krótką wnęką rezonansową o małej rozdzielczości. Walorami takiego rozwiązania są m.in. prosta i zwarta budowa, niska cena, mały wpływ temperatury oraz brak zaniku obrazu interferencyjnego wywołanego polaryzacją. W związku z możliwością obciążeń transformatorów, zakłady elektroenergetyczne oraz firmy prowadzące eksploatację testują transformatory mocy w celu oceny ich stanu, ustalenia harmonogramu prac konserwacyjnych i zaplanowania wymiany. Najczęściej stosowany jest pomiar temperatury.
Źródło:
Physics for Economy; 2019, 3, 1; 5-13
2544-7742
2544-7750
Pojawia się w:
Physics for Economy
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Diagnosis of the Non-Concurrent Operation of the On-Load Tap Changer Contacts by the Acoustic Emission Method
Autorzy:
Cichoń, A.
Borucki, S.
Boczar, T.
Powiązania:
https://bibliotekanauki.pl/articles/177044.pdf
Data publikacji:
2011
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
power transformer
on-load tap changers
acoustic emission method
Opis:
On-load tap changers (OLTC) are some of the main transformer elements that make voltage adjustment in a power network possible. Their failures often cause shutdowns of distribution transformers. The paper presents research work aimed at the assessment of the technical condition of OLTCs by the acoustic emission method (EA). This method makes the OLTC diagnosis possible without the need of disconnecting the transformer from the system. The measurements were taken in laboratory conditions. The influence on the operation non-concurrence of the power tap changer contacts on the AE registered signals has been investigated. The signals registered were subjected to analyses in the time and time-frequency domains. The result analysis in the time domain was carried out using the Hilbert transform and calculating characteristic times for the particular runs. A short-time Fourier transform was used for the assessment of results in the time-frequency do- main.
Źródło:
Archives of Acoustics; 2011, 36, 4; 823-830
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Analiza działania zabezpieczenia podimpedancyjnego dwukadziowego symetrycznego przesuwnika fazowego
Analysis of protection operation under impedance double tank symmetric phase shifting transformer
Autorzy:
Bednarczyk, T.
Halinka, A.
Rzepka, P.
Szablicki, M.
Powiązania:
https://bibliotekanauki.pl/articles/267229.pdf
Data publikacji:
2017
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
przesuwnik fazowy
automatyka zabezpieczeniowa
transformator
zakłócenia
Phase Shifting Transformer
power system protection
power transformer
disturbances
Opis:
Zabezpieczenie wykorzystujące kryterium podimpedancyjne stanowi jedno z podstawowych zabezpieczeń jednostek transformatorowych najwyższych napięć (w tym przesuwników fazowych). Zabezpieczenie podimpedancyjne identyfikuje stan pracy chronionego przesuwnika fazowego, sprawdzając położenie końca wektora impedancji wyznaczanej w zabezpieczeniu względem stref pomiarowych zabezpieczenia. Podczas zwarć w obrębie fragmentu sieci objętego ochroną przez zabezpieczenie, koniec wektora impedancji powinien „wchodzić” do stref pomiarowych zabezpieczenia. Wówczas następuje zadziałanie zabezpieczenia i ewentualne wyłączenie przesuwnika fazowego. W artykule zamieszczono wyniki przeprowadzonych badań symulacyjnych warunków działania zabezpieczenia podimpedancyjnego dla dwukadziowego symetrycznego przesuwnika fazowego. W symulacjach uwzględniono szeroki zakres zmian impedancji przesuwnika fazowego, zwarcia wewnętrzne oraz zewnętrzne. Wyniki badań symulacyjnych pozwalają na weryfikację poprawności działania zabezpieczenia podimpedancyjnego przesuwnika fazowego.
Relay protection using criterion under impedance is one of the basic security units high voltage transformer (including phase shifters - PST, ang. Phase Shifting Transformer). Protection under impedance identifies the operating status of the protected PST, checking the position of the end vector impedance to be fixed in terms of securing zones measuring security. While short-circuits within the network portion of the end vector impedance should "enter" zones measuring security. Then followed by a safety device and possible exclusion PST. The article contains the results of the simulation tests of operating conditions for security under impedance doubletransformer tank dwukadziowego symmetric phase shifter. The simulations take into account a wide range of impedance changes PST, short circuit, internal and external. The results of simulation studies allow for verification of correct operation of security under impedance PST.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2017, 53; 71-74
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Using Clustering Methods for the Identification of Acoustic Emission Signals Generated by the Selected Form of Partial Discharge in Oil-Paper Insulation
Autorzy:
Borucki, S.
Łuczak, J.
Zmarzły, D.
Powiązania:
https://bibliotekanauki.pl/articles/177657.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
acoustic emission method
acoustic signals
partial discharges
insulation
power transformer
Opis:
The article presents the results concerning the use of clustering methods to identify signals of acoustic emission (AE) generated by partial discharge (PD) in oil-paper insulation. The conducted testing featured qualitative analysis of the following clustering methods: single linkage, complete linkage, average linkage, centroid linkage and Ward linkage. The purpose of the analysis was to search the tested series of AE signal measurements, deriving from three various PD forms, for elements of grouping (clusters), which are most similar to one another and maximally different than in other groups in terms of a specific feature or adopted criteria. Then, the conducted clustering was used as a basis for attempting to assess the effectiveness of identification of particular PD forms that modelled exemplary defects of the power transformer’s oil-paper insulation system. The relevant analyses and simulations were conducted using the Matlab estimation environment and the clustering procedures available in it. The conducted tests featured analyses of the results of the series of measurements of acoustic emissions generated by the basic PD forms, which were obtained in laboratory conditions using spark gap systems that modelled the defects of the power transformer’s oil-paper insulation.
Źródło:
Archives of Acoustics; 2018, 43, 2; 207-215
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Design of Transformers
Projektowanie transformatorów
Autorzy:
Kornas, T.
Powiązania:
https://bibliotekanauki.pl/articles/396980.pdf
Data publikacji:
2016
Wydawca:
ENERGA
Tematy:
transformator mocy
projektowanie
budowa
kadź
power transformer
design
construction
tank
Opis:
In this paper the basic designing of high voltage power transformers has been described. The layout and construction of a high voltage and low voltage winding of transformers has been determined. The designing of a tank of transformers has also been considered.
W artykule przedstawiono podstawy projektowania transformatorów mocy wysokiego napięcia. Określono konstrukcję i rozłożenie uzwojenia wysokiego i niskiego napięcia. Przedstawiono również projekt kadzi transformatora.
Źródło:
Acta Energetica; 2016, 4; 40-50
2300-3022
Pojawia się w:
Acta Energetica
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
A Power Transformer as a Source of Noise
Autorzy:
Zawieska, W. M.
Powiązania:
https://bibliotekanauki.pl/articles/90466.pdf
Data publikacji:
2007
Wydawca:
Centralny Instytut Ochrony Pracy
Tematy:
power transformer
noise reduction
active methods
transformer modeling
rectangular plate vibrations
transformer noise
vibroacoustic analysis
Opis:
This article presents selected results of analyses and simulations carried out as part of research performed at the Central Institute of Labor Protection – the National Research Institute (CIOP-PIB) in connection with the development of a system for active reduction of noise emitted by high power electricity transformers. This analysis covers the transformer as a source of noise as well as a mathematical description of the phenomenon of radiation of vibroacoustic energy through a transformer enclosure modeled as a vibrating rectangular plate. Also described is an acoustic model of the transformer in the form of an array of loudspeakers.
Źródło:
International Journal of Occupational Safety and Ergonomics; 2007, 13, 4; 381-389
1080-3548
Pojawia się w:
International Journal of Occupational Safety and Ergonomics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
The Application of Selected Hierarchical Clustering Methods for Classification the Acoustic Emission Signals Generated by Partial Discharges
Autorzy:
Borucki, Sebastian
Łuczak, Jacek
Lorenc, Marcin
Powiązania:
https://bibliotekanauki.pl/articles/2097707.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Czasopisma i Monografie PAN
Tematy:
acoustic emission method
acoustic signals
partial discharges
power transformer
clustering method
Opis:
The paper presents the results of the application of the hierarchical clustering methods for the classification of the acoustic emission (AE) signals generated by eight basic forms of partial discharges (PD), which can occur in paper-oil insulation of power transformers. Based on the registered AE signals from the particular PD forms, using a frequency descriptor in the form of the power spectral density (PSD) of the signal, their representation in the form of the set of points on plane XY was created. Next, these sets were subjected to analysis using research algorithms consisting of selected clustering methods. Based on the suggested numeric performance indicators, the analysis of the degree of reproduction of the actual distribution of points showing the particular time waveforms of the AE signals from eight adopted PD forms (PD classes) in the obtained clusters was carried out. As a result of the analyses carried out, the clustering algorithms of the highest effectiveness in the identification of all eight PD classes, classified simultaneously, where indicated. Within the research carried out, an attempt to draw general conclusions as to the selection of the most effective hierarchical clustering method studied and the similarity function to be used for classification of the selected basic PD forms.
Źródło:
Archives of Acoustics; 2021, 46, 3; 409-417
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Oszacowanie zawilgocenia izolacji celulozowej na podstawie zawartości wody w oleju
: Estimation of moisture content in cellulose insulation on the basis of moisture content in oil
Autorzy:
Bocheński, B.
Lutkowski, F.
Powiązania:
https://bibliotekanauki.pl/articles/156525.pdf
Data publikacji:
2008
Wydawca:
Stowarzyszenie Inżynierów i Techników Mechaników Polskich
Tematy:
transformator energetyczny
izolacja papierowo-olejowa transformatora
zawilgocenie
power transformer
paper-oil transformer insulation
moisture content
Opis:
W referacie przedstawiony został problem pomiaru zawilgocenia izolacji celulozowej w transformatorze z izolacją papierowo-olejową oraz możliwości oszacowania jej na podstawie zawartości wody w oleju. Ponadto w referacie zaprezentowane zostały wyniki prac nad opracowaniem modelu numerycznego migracji wody z izolacji celulozowej do oleju i zastosowanie ich w opracowanym programie komputerowym.
The objective of this paper is to present the problem of measuring moisture content in paper insulation of a power transformer. Even though there is still no possibility of taking direct measurement of moisture content in the cellulose insulation, it can be estimated based on measurement result of moisture content in the oil. Additionally, some equations which were formulated for modeling water migration between cellulose and oil are given.
Źródło:
Pomiary Automatyka Kontrola; 2008, R. 54, nr 11, 11; 773-776
0032-4140
Pojawia się w:
Pomiary Automatyka Kontrola
Dostawca treści:
Biblioteka Nauki
Artykuł

Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies