Tytuł:
A fault diagnosis method for substation grounding grid based on the square-wave frequency domain model
Autorzy:
Zhang, P.-H.
He, J.-J.
Zhang, D.-D.
Wu, L.-M.
Powiązania:
https://bibliotekanauki.pl/articles/221635.pdf
Data publikacji:
2012
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
square-wave
frequency characteristics
grounding grid
fault diagnosis
Opis:
Current methods of fault diagnosis for the grounding grid using DC or AC are limited in accuracy and cannot be used to identify the locations of the faults. In this study, a new method of fault diagnosis for substation grounding grids is proposed using a square-wave. A frequency model of the grounding system is constructed by analyzing the frequency characteristics of the soil and the grounding conductors into which two different frequency square-wave sources are injected. By analyzing and comparing the corresponding information of the surface potentials of the output signals, the faults of the grounding grid can be diagnosed and located. Our method is verified by software simulation, scale model experiments and field experiments.
Źródło:
Metrology and Measurement Systems; 2012, 19, 1; 63-71
0860-8229
Pojawia się w:
Metrology and Measurement Systems
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Modeling transients in MV resonantly grounded industrial grid during single line to ground faults
Autorzy:
Warecki, Jurij
Gajdzica, Michał
Powiązania:
https://bibliotekanauki.pl/articles/377060.pdf
Data publikacji:
2019
Wydawca:
Politechnika Poznańska. Wydawnictwo Politechniki Poznańskiej
Tematy:
electrical grid
grounding methods
transients overvoltage
transient intermittent faults
Opis:
Medium voltage distribution power grids mostly operate with ungrounded neutral points of transformer. The philosophy about these power supply systems based on the assumption that the electrical grid is more reliable. However the practice of operation showed that currents of single phase or multiple faults to ground depend mostly on the earth capacitances of cables connected to power grid and configuration and structure in relation to the main substation buses. Moreover, this kind of arcing ground faults on the ungrounded system causes transient overvoltages several times than nominal value. In the consequence, it may be dangerous for the electrical devices connected to the power system. The article focuses on the transient impact the equipment insulation due to faults in the middle voltage industrial grid with adjustable speed drives. The examination results of transient voltages across the system was presented. The Matlab/ Simulink Software was used to modeling system behavior during intermittent faults.
Źródło:
Poznan University of Technology Academic Journals. Electrical Engineering; 2019, 98; 65-75
1897-0737
Pojawia się w:
Poznan University of Technology Academic Journals. Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-2 z 2

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies