Medium voltage distribution power grids mostly operate with ungrounded neutral
points of transformer. The philosophy about these power supply systems based on the
assumption that the electrical grid is more reliable. However the practice of operation
showed that currents of single phase or multiple faults to ground depend mostly on the
earth capacitances of cables connected to power grid and configuration and structure in
relation to the main substation buses. Moreover, this kind of arcing ground faults on the
ungrounded system causes transient overvoltages several times than nominal value. In
the consequence, it may be dangerous for the electrical devices connected to the power
system. The article focuses on the transient impact the equipment insulation due to faults
in the middle voltage industrial grid with adjustable speed drives. The examination results
of transient voltages across the system was presented. The Matlab/ Simulink Software
was used to modeling system behavior during intermittent faults.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies