- Tytuł:
- Problems and counter measures of arc suppression coilin 10 kV distribution system
- Autorzy:
-
Ni, Hui
Ding, Pei
Ma, Yunlong
Ai, Shaogui
Ma, Feiyue
Zhang, Qingping - Powiązania:
- https://bibliotekanauki.pl/articles/141485.pdf
- Data publikacji:
- 2019
- Wydawca:
- Polska Akademia Nauk. Czytelnia Czasopism PAN
- Tematy:
-
arc suppression coil
capacitive current
artificial grounding fault test
neutral non-effective grounding system - Opis:
- The arc suppression coil determines whether it can effectively extinguish the arc when it is grounded in the neutral non-effective grounding system. An artificial grounding test is an importantway to verify its performance. In this study, 13 substations with the 10 kV system in the Ningxia areawere selected and considered. Based on the artificial single-phase grounding test, the residual current, the compensation current and the off-resonance degree were measured in the arc suppression coil, and the performance of the arc suppression coil in the 10 kV system was verified. The experimental results show that the error of arc suppression coil automatic measurement is large, the off-resonance degree is large, the resistive component in the compensation current is excessive, the harmonic component exists in the compensating current and capacitive current. To solve these problems, this paper puts forward the corresponding countermeasures for reference.
- Źródło:
-
Archives of Electrical Engineering; 2019, 68, 1; 135-146
1427-4221
2300-2506 - Pojawia się w:
- Archives of Electrical Engineering
- Dostawca treści:
- Biblioteka Nauki