The arc suppression coil determines whether it can effectively extinguish the arc
when it is grounded in the neutral non-effective grounding system. An artificial grounding
test is an importantway to verify its performance. In this study, 13 substations with the 10 kV
system in the Ningxia areawere selected and considered. Based on the artificial single-phase
grounding test, the residual current, the compensation current and the off-resonance degree
were measured in the arc suppression coil, and the performance of the arc suppression
coil in the 10 kV system was verified. The experimental results show that the error of arc
suppression coil automatic measurement is large, the off-resonance degree is large, the
resistive component in the compensation current is excessive, the harmonic component
exists in the compensating current and capacitive current. To solve these problems, this
paper puts forward the corresponding countermeasures for reference.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies