- Tytuł:
- Resonance mechanisms of a single line-to-ground fault on ungrounded systems
- Autorzy:
-
Jiang, Jun
Liu, Ling - Powiązania:
- https://bibliotekanauki.pl/articles/141380.pdf
- Data publikacji:
- 2020
- Wydawca:
- Polska Akademia Nauk. Czytelnia Czasopism PAN
- Tematy:
-
power distribution faults
single line-to-ground fault
transient characteristics
ungrounded distribution system - Opis:
- As for a single line-to-ground fault in an ungrounded distribution system, the power-frequency current is too low to detect the fault. The transient current is more palpable than that at a power-frequency of 50 or 60 Hz. It is an effective method to estimate the fault using the transient fault current. To analyze and calculate the transient current of single line-to-ground faults, an equivalent circuit is proposed in this paper. This model is based on distributed parameters of power lines. And it contains positive, negative and zero sequence information. The transient equivalent circuit consists of equivalent resistance, equivalent inductance and equivalent capacitance. And the method of calculation the equivalent elements is also submitted. MATLAB simulation results show that the new transient equivalent circuit has higher accuracy and stronger adaptability compared with the traditional one.
- Źródło:
-
Archives of Electrical Engineering; 2020, 69, 2; 455-466
1427-4221
2300-2506 - Pojawia się w:
- Archives of Electrical Engineering
- Dostawca treści:
- Biblioteka Nauki