Tytuł:
Tutorial on operating characteristics of microprocessor-based multiterminal line current differential relays
Autorzy:
Kasztenny, B
Benmouyal, G
Altuve, H J
Fischer, N
Powiązania:
https://bibliotekanauki.pl/articles/410604.pdf
Data publikacji:
2013
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
protective relaying
differential protection
Alpha Plane principle
Opis:
Line current differential (87L) protection schemes face extra challenges compared with other forms of differential protection, in addition to the traditional requirements of sensitivity, speed, and immunity to current transformer saturation. Some of these challenges include data communication, alignment, and security; line charging current; and limited communications bandwidth. To address these challenges, microprocessor-based 87L relays apply elaborate operating characteristics, which are often different than a traditional percentage differential characteristic used for bus or transformer protection. These sophisticated elements may include adaptive restraining terms, apply an Alpha Plane, use external fault detection logic for extra security, and so on. While these operating characteristics provide for better performance, they create the following challenges for users: x Understanding how the 87L elements make the trip decision. x Understanding the impact of 87L settings on sensitivity and security, as well as grasping the relationship between the traditional percentage differential characteristic and the various 87L operating characteristics. x Having the ability to transfer settings between different 87L operating characteristics while keeping a similar balance between security and dependability. x Testing the 87L operating characteristics. These issues become particularly significant in applications involving more than two currents in the line protection zone (multiterminal lines) and lines terminated on dual-breaker buses. This paper is a tutorial on this relatively new protection topic and offers answers to the outlined challenges.
Źródło:
Present Problems of Power System Control; 2013, 3; s. 5-73
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Generator split-phase protection
Autorzy:
Kim, S.
Finney, D.
Fischer, N.
Kasztenny, B.
Powiązania:
https://bibliotekanauki.pl/articles/410559.pdf
Data publikacji:
2012
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
protective relaying
stator differential protection
split-phase protection
Opis:
The stator winding of a hydrogenerator is often made up of coils with multiple turns in the same slot. It is therefore possible for faults to develop between adjacent turns on the same phase (turn-toturn faults). These faults cannot be detected by the stator differential protection because there is no difference between the neutral- and terminal-side currents. Split-phase protection, an overcurrent element responding to the difference between the currents in the winding parallel branches, is typically provided to detect these faults. Ideally, the split-phase element should be sensitive enough to detect a single shorted turn. Despite the fact that the current in this turn can be six to seven times the machine nominal current, the current seen by the split-phase protection can be quite small, in the order of one-twentieth of the generator full-load current. In addition, a spurious split-phase current can be measured due to current transformer (CT) errors, saturation during external faults in particular. Therefore, primary considerations in the application of split-phase protection are the method of measuring the difference in the currents between the parallel branches and the proper selection of the CT used for this purpose.
Źródło:
Present Problems of Power System Control; 2012, 2; 5-40
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
New method of CT saturation detection
Autorzy:
Bąk, D.
Dong, X.
Rebizant, W.
Powiązania:
https://bibliotekanauki.pl/articles/410533.pdf
Data publikacji:
2012
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
CT saturation detection
protective relaying
transient analysis
Opis:
A new method for detection of CT saturation is presented in this paper. The presented algorithm applies a new, innovative methodology mapping first order derivative of phase current signals into coordinates of a 3D vector. The comparison of proposed algorithm with standard one based on secondary current signal's second derivative is conducted and some of simulation results are presented to show the proposed algorithm effectiveness.
Źródło:
Present Problems of Power System Control; 2012, 2; 65-72
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-3 z 3

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies