Thermal calculation for distance protection enhancement
Autorzy:
Staszewski, Ł
Rebizant, W
Powiązania:
https://bibliotekanauki.pl/articles/410608.pdf
Data publikacji:
2013
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
dynamic thermal line rating
distance protection
power swing
third zone
Opis:
Worldwide analysis of recent wide area cascading failures has shown that very often their main cause was the mal-operation of the distance protection relay third zone. The load encroachment and power swing phenomena are the two dire problems to solve when dealing with the third zone of distance protection. The vast number of blackouts could have been avoided or the consequences lowered if the distance relay had not operated due to impedance encroachment while there was no risk of further, continuous operation. This paper proposes a way to improve operation of the distance protection relay by introducing a new blocking algorithm that uses the Dynamic Thermal Line Rating (DTLR) to restrain relay from tripping when conditions in electrical power system allow for it.
Źródło:
Present Problems of Power System Control; 2013, 3; s. 83-94
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Study of the impact of 220 kV SISFCL on the distance protection for transmission line
Autorzy:
Luo, Y.
Shi, T.
Huang, L.
Powiązania:
https://bibliotekanauki.pl/articles/141728.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
SISFCL
distance protection
EMTDC/PSCAD
220 kV transmission line
setting method
Opis:
As the most typical application of superconducting technology, the Saturated Iron core Superconducting Fault Current Limiter (SISFCL) is a kind of ideal high voltage limiter, which can achieve noticeable limiting endless stream and has wide application prospect. However, the selectivity and sensitivity of the distance protection (DP) in the high voltage transmission network would be affected by the impedance characteristics of SISFCL. For these problems, firstly the structure and the working principle of the SISFCL are introduced briefly. Secondly, the impact mechanisms of 220 kV SISFCL on the original distance protection for the transmission line (TL) are analyzed. Then two methods of eliminating influences are deduced from the previous analysis and an improved setting method based on SISFCL for distance protection is proposed. Finally, we used EMTDC/PSCAD software to build the 220 kV SISFCL and distance protection model in the transmission network. The simulation results demonstrate that the proposed setting strategy can effectively improve the selectivity and sensitivity of distance protection and provide a reference for the practical applications of SISFCL applied to the transmission line.
Źródło:
Archives of Electrical Engineering; 2018, 67, 1; 151-163
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Profesor Tadeusz Łobos i jego algorytm A4
Professor Tadeusz Llobos and his A4 algorithm
Autorzy:
Chrzan, K. L.
Powiązania:
https://bibliotekanauki.pl/articles/1203359.pdf
Data publikacji:
2018
Wydawca:
Sieć Badawcza Łukasiewicz - Instytut Napędów i Maszyn Elektrycznych Komel
Tematy:
cyfrowa ochrona linii
algorytmy identyfikacji zwarć
algorytm Łobosa
algorytm A4
digital line protection
algorithms for distance protection
Lobos’s algorithm A4
Opis:
This document shows cirriculum vitae, scientific work and achievement of Prof. Tadeusz Łobos. The most known his achievement is algorithm A3 and especially algorithm A4. This second one was many times referred and explained in reading books. What is visible in his carrier it is a very intensive co-operation with German scientists. During 48 years scientific activity he spent over 10 years in Germany in the frame of 13 different scholarships and on the 4 years long contract in Darmstadt, Erlangen, Saarbruecken and Dresden. As alone from polish electrical engineers he became the prestigious Humboldt Research Award. Tadeusz Łobos published over 300 articles and conference papers, got 7 patents and was the supervisor of 13 doctor theses.
W pracy opisano życiorys, pracę naukową i osiągnięcia prof. Tadeusza Łobosa. Najbardziej znanym jego osiągnięciem są algorytmy Łobosa A3, a szczególnie algorytm A4 wielokrotnie cytowany i opisany w książkach. Zwraca uwagę niezwykle intensywna współpraca z partnerami niemieckimi. W ciągu swej 48 letniej pracy naukowej, przebywał w sumie ponad 10 lat na co najmniej 13 stypendiach oraz 4-letnim kontrakcie w Darmstadzie, Erlangen, Saarbruecken i Dreźnie. Jako jedyny polski elektrotechnik otrzymał prestiżową Humboldt Research Award, opublikował ponad 300 artykułów i referatów konferencyjnych, otrzymał 7 patentów i był promotorem 13 prac doktorskich.
Źródło:
Maszyny Elektryczne: zeszyty problemowe; 2018, 4, 120; 143-147
0239-3646
2084-5618
Pojawia się w:
Maszyny Elektryczne: zeszyty problemowe
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Koncepcja obszarowego algorytmu pomiarowego zabezpieczenia odległościowego linii dla zwarć jednofazowych
The concept of area measurement algorithm of line distance protection for single-phase faults
Autorzy:
Szablicki, Mateusz
Halinka, Adrian
Rzepka, Piotr
Powiązania:
https://bibliotekanauki.pl/articles/266604.pdf
Data publikacji:
2019
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
elektroenergetyczna automatyka zabezpieczeniowa
zabezpieczenie odległościowe linii
algorytm pomiarowy
power system protection
line distance protection
measurement algorithm
Opis:
Klasyczne zabezpieczenia odległościowe, obecnie stosowane w liniach WN i NN, identyfikują stan pracy chronionej linii, kontrolując parametry impedancji pętli zwarcia. Powoduje to dużą wrażliwość poprawności ich działania na czynniki fałszujące „pomiar” impedancji. Jest to podyktowane wyznaczaniem impedancji wyłącznie na podstawie sygnałów napięciowych i prądowych dostępnych lokalnie, w miejscu zainstalowania zabezpieczenia. Dotyczy to zarówno zwarć wielofazowych, jak i jednofazowych. Dla zwarć wielofazowych autorzy opracowali koncepcję nowych algorytmów wyznaczania impedancji, dla których wykazano niewrażliwość na czynniki fałszujące występujące w zabezpieczeniach klasycznych. W publikacji przedstawiono koncepcję tożsamego algorytmu dedykowanego dla zwarć jednofazowych. Zamieszczono także wyniki badań symulacyjnych dowodzących poprawności tego algorytmu.
Classic line distance protection, previously used in high and extra high voltage, are sensitive to factors falsifying the measurement of impedance (among others: non-zero fault resistance, fault leakage current phenomenon, passive and active outflow of the power line). This determines the high risk of incorrect operation of these protections. As a result, this may lead to unwanted switching off the line which work normal network conditions or the lack of the required shutdown the line affected by the fault. The main cause of incorrect operation of the power line protection is identification of the line operation status based on the impedance determined by the measurement algorithm based only on voltage and current signals available locally at the protection location. This applies to phase-to-phase faults and single-phase faults. For phase faults authors have already developed the concept of new measurement algorithms. Simulations and laboratory study have demonstrated the insensitivity of these algorithms to the factors falsifying the operation of classical distance protections. Currently, the authors have defined a similar concept a new measurement algorithm dedicated to single-phase faults. The publication presents equations this new algorithm and the results of simulation verification tests.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2019, 62; 131-134
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Distance protection with dynamic thermal line rating enhancement
Autorzy:
Staszewski, Ł.
Rebizant, W.
Powiązania:
https://bibliotekanauki.pl/articles/410531.pdf
Data publikacji:
2012
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
dynamic thermal line rating
distance protection
overload
heat balance
Opis:
As the worldwide analysis of recent wide area cascading failures have shown, very often the main cause of blackout was mal-operation of the third zone of a distance protection relay. The load encroachment and power swing phenomena are the two dire problems to solve when dealing with the third zone of distance protection mal-function. The vast number of blackouts could have been avoided or the consequences lowered if the distance relay had not operated due to controlled impedance encroachment.This paper proposes a new approach to enhance the distance protection relay operation by introducing a new blocking algorithm. The algorithm is based on Dynamic Thermal Line Rating (DTLR) idea to restrain relay from tripping when conditions in electrical power system and weather conditions allow for it.
Źródło:
Present Problems of Power System Control; 2012, 2; 73-84
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Badanie poprawności pomiarowej i decyzyjnej cyfrowych i analogowych zabezpieczeń odległościowych – wybrane aspekty
Testing correctness of measuring and decision making of analog and digital distance protection
Autorzy:
Bednarczyk, T.
Nandzik, P.
Powiązania:
https://bibliotekanauki.pl/articles/1199587.pdf
Data publikacji:
2017
Wydawca:
Sieć Badawcza Łukasiewicz - Instytut Napędów i Maszyn Elektrycznych Komel
Tematy:
automatyka zabezpieczeniowa sieci wysokich napięć
analiza parametrów sieci 110 kV
zabezpieczenia odległościowe linii WN
system protection high-voltage network
analysis parameters power system 110 kV
line distance protection
Opis:
In this paper they were conducted laboratory tests in order to verify the accuracy of the measurement and decision-making of selected distance protection in the execution of digital and analogue. Were carried out based on actual measurements of the distribution network parameters 110 kV, analyzing the frequency deviation and content of higher harmonic currents and phase voltages.
Ciągły postęp ewolucyjny systemu elektroenergetycznego wymaga również dopasowania do zmieniających się warunków stosowanych środków ochrony przed skutkami zakłóceń. W tym zakresie m.in. dokonywana jest wymiana analogowych przekaźników zabezpieczeniowych na ich cyfrowych następców. Zmiany często prowadzą do refleksji czy taka zmiana technologii prowadzi do polepszenia czy do pogorszenia ochrony systemu elektroenergetycznego. Biorąc pod uwagę zabezpieczenia odległościowe linii WN, przeprowadzono serię wybranych testów reprezentatywnych egzemplarzy zabezpieczeń analogowych i cyfrowych mających na celu uzyskanie w określonym zakresie odpowiedzi na postawione pytanie.
Źródło:
Maszyny Elektryczne: zeszyty problemowe; 2017, 1, 113; 183-188
0239-3646
2084-5618
Pojawia się w:
Maszyny Elektryczne: zeszyty problemowe
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Badania zakłóceniowe algorytmu pomiarowego oraz decyzyjnego cyfrowych i analogowych zabezpieczeń odległościowych linii
Transient studies of the measurement and decision algorithm of digital and analog distance protection systems
Autorzy:
Bednarczyk, T.
Powiązania:
https://bibliotekanauki.pl/articles/302800.pdf
Data publikacji:
2018
Wydawca:
Wydawnictwo Druk-Art
Tematy:
automatyka zabezpieczeniowa sieci wysokich napięć
analiza parametrów sieci 110 kV
zabezpieczenia odległościowe linii WN
system protection high-voltage network
analysis parameters power system 110 kV
line distance protection
Opis:
Ciągły postęp ewolucyjny systemu elektroenergetycznego wymaga dopasowania środków ochrony przed skutkami zakłóceń do zmieniających się warunków stosowanych. W tym zakresie m.in. dokonywana jest wymiana analogowych przekaźników zabezpieczeniowych na ich cyfrowych następców. Zmiany często prowadzą do refleksji, czy taka zmiana technologii prowadzi do polepszenia, czy do pogorszenia ochrony systemu elektroenergetycznego. Biorąc pod uwagę zabezpieczenia odległościowe linii WN, przeprowadzono serię wybranych testów reprezentatywnych egzemplarzy zabezpieczeń analogowych i cyfrowych, mających na celu uzyskanie w określonym zakresie odpowiedzi na postawione pytanie.
In this paper, they were conducted laboratory tests in order to verify the accuracy of the measurement and decision-making of selected distance protection in the execution of digital and analogue. Were carried out based on actual measurements of the distribution network parameters 110 kV, analyzing the frequency deviation and content of higher harmonic currents and phase voltages.
Źródło:
Napędy i Sterowanie; 2018, 20, 5; 74-79
1507-7764
Pojawia się w:
Napędy i Sterowanie
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Analiza warunków działania zabezpieczeń odległościowych linii w sieciach elektroenergetycznych z układami HVDC LCC
Analysis of operations for line distance protection in power networks with LCC-HVDC systems
Autorzy:
Szablicki, Mateusz
Rzepka, Piotr
Halinka, Adrian
Powiązania:
https://bibliotekanauki.pl/articles/268641.pdf
Data publikacji:
2019
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
HVDC
zabezpieczenie odległościowe linii
parki energii z podłączeniem prądu stałego
distance protection line
DC-connected power parks modules
Opis:
Układy HVDC znajdują coraz szersze zastosowanie w elektroenergetyce, m.in. jako elementy wymiany mocy między układami sieciowymi pracującymi niesynchronicznie lub elementy wyprowadzenia mocy z parków energii z podłączeniem prądu stałego. Jednak dotychczas często stosowana w nich technologia LCC wykazuje dużą podatność na przewroty komutacyjne. Towarzyszą im gwałtowne zmiany napięć i prądów w otoczeniu układu HVDC. Może to prowadzić m.in. do niepoprawnego działania zabezpieczeń odległościowych linii i stanowić zagrożenie dla bezpiecznej pracy sieci i jej użytkowników. Publikacja zawiera wyniki oceny możliwego negatywnego oddziaływania układów HVDC LCC na te podstawowe zabezpieczenia linii NN i WN. Taka ocena jest szczególnie istotna obecnie, w perspektywie wielu zapowiadanych inwestycji w układy HVDC.
High Voltage Direct Current (HVDC) systems are increasingly used in power networks. However, usually used in them LCC (Line Commutated Converters) technology causes high susceptibility to commutation failures. Significant changes in network operation conditions accompany this phenomenon. This is manifested, among others violent and significant changes in the values of voltages and currents in the vicinity of the HVDC system. These voltages and current are used by distance protection lines to identify the actual state of the line. This causes that commutation failures in the HVDC system may lead to incorrect operation of distance protection line and unjustified switching off the line or lack of required line shutdown. Incorrect operation of the distance protection may be dangerous for the safe operation of the line, other power network objects and electricity consumers. The paper shows the recognition and accurate characterization of potential scale of abnormalities in the operation of distance protection lines, which work in the vicinity of the HVDC systems. It is emphasized that the subject of the paper is particularly important now. This is dictated by the multitude of announced investments in HVDC systems, primarily as a component of strongly promoted off-shore energy parks.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2019, 62; 123-126
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-8 z 8

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies