Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "VSC-MTDC" wg kryterium: Temat


Wyświetlanie 1-3 z 3
Tytuł:
Research on influencing factors of emergency power support for voltage source converter-based multi-terminal high-voltage direct current transmission system
Autorzy:
Li, Congshan
Zhen, Zikai
Sheng, Tingyu
Liu, Yan
Zhong, Pu
Zhang, Xiaowei
Powiązania:
https://bibliotekanauki.pl/articles/2172797.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
coordinated control
emergency DC power support
influencing factors
VSC- MTDC transmission
Opis:
Voltage source converter-based multi-terminal high-voltage direct current (VSCMTDC) transmission system can realize a multi-point power supply, multi-drop power receiving, and mutual coordination between the converter stations to ensure the reliability of the transmission. Based on the PSCAD/EMTDC platform, a five-terminal DC transmission system model is established. According to the fast power regulation capability and overload capacity of theVSC-MTDC power transmission system, an analysis of additional emergency power support for a transmission system under large disturbance conditions was carried out. A new control strategy for emergency power support that introduces its basic principle is proposed in this paper. It uses the short-term overload capability of the DC system. By changing the power reserve of the converter station and the electrical distance between the converter stations, the influence of the power reserve and the electrical distance on the emergency power supply guarantee is analyzed the stability of the system is improved, thereby improving the sudden change of power caused by voltage fluctuations, and the feasibility of the control module is verified by PSCAD simulation. The simulation results show that when the system power supply suddenly changes, the converter stations at a short distance and large power reserve has a better effect on emergency power supply protection. A comparative study of the active power support of a single converter station and multiple converter stations is carried out. The research results show that the use of emergency power support in the DC transmission system has a good effect on maintaining the stability of the inter-connection system and the reliability of the power supply.
Źródło:
Archives of Electrical Engineering; 2022, 71, 4; 881--894
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Distributed collaborative optimization DC voltage control strategy for VSC–MTDC system with renewable energy integration
Autorzy:
Li, Jingye
Dong, Haiyimg
Powiązania:
https://bibliotekanauki.pl/articles/2086694.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
DC voltage control
distributed model prediction
droop control
VSC–MTDC
PSCAD/EMTDC
Opis:
Aiming at the problem of DC voltage control deviation and instability caused by a large-scale renewable energy access VSC–MTDC system, this paper combines voltage margin control and droop control. A strategy for controlling collaborative optimization in a sparsely distributed communication network has been proposed. Firstly, the distributed modeling of the system is carried out by combining MAS technology with small signal modeling. Then, a distributed model predictive controller is designed for a single droop control converter station. On this basis, a distributed cooperative optimization control strategy is proposed. According to the DC voltage deviation, the system adopts different control methods to control the receiving converter station. Finally, based on PSCAD/EMTDC and MATLAB co-simulation platforms, a six-terminal flexible HVDC system is built to verify the effectiveness of the control strategy under different conditions such as input power fluctuation, any converter station out of operation and system communication failure.
Źródło:
Archives of Electrical Engineering; 2022, 71, 2; 325--342
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Research on regional emergency DC power support strategy of VSC-MTDC transmission system
Autorzy:
Li, Congshan
Sheng, Tingyu
Fang, Yan
Li, Yikai
Powiązania:
https://bibliotekanauki.pl/articles/1841327.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
coordinated control
dynamic active power support
emergency DC power support
VSC-MTDC
skoordynowana kontrola
dynamiczne wspomaganie mocy czynnej
awaryjne wsparcie zasilania prądem stałym
Opis:
In the asynchronous interconnected power grid that is composed of the multiterminal voltage-source converter high voltage direct current (VSC-MTDC) system, the control methods of each converter station and the frequency of the connected AC systemare not the same. When a fault occurs in any place of the asynchronous interconnected system, it will cause the system to have power shortage or surplus, affecting the safe and stable operation of the interconnected power grid. In order to solve the problem of insufficient regional active power reserve, based on the VSC-MTDC asynchronous regional interconnection system and the principle of regional sharing, the dynamic power controller under disturbance conditions is established, and the controller parameters are set to achieve the accuracy of unbalanced power in the disturbance area measuring. Then, according to the degree of the disturbance power, considering the factors that affect the support effect of the converter station, an emergency DC power support (EDCPS) scheme under different power disturbances is formulated to achieve power compensation for the disturbance area. Basedon PSCAD/EMTDC software, the proposed control strategy is simulated. The result showst hat the converter station closer to the disturbance area has a better support effect, and the dynamic active power controller can timely and accurately deliver to the disturbance area when the active power reserve is insufficient.
Źródło:
Archives of Electrical Engineering; 2021, 70, 1; 145-160
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-3 z 3

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies