- Tytuł:
- An improved algorithm for the series step-up method based on a linear three-ports network
- Autorzy:
-
Liu, Hao
Chen, Lixue
Wang, Xue
Yao, Teng
Gu, Xiong - Powiązania:
- https://bibliotekanauki.pl/articles/2106422.pdf
- Data publikacji:
- 2022
- Wydawca:
- Polska Akademia Nauk. Czytelnia Czasopism PAN
- Tematy:
-
voltage transformer
traceability method
calibration
high voltage - Opis:
- Capacitive leakage and adjacent interference are the main influence sources of the measuring error in the traditional series step-up method. To solve the two problems, a new algorithm was proposed in this study based on a three-ports network. Considering the two influences, it has been proved that response of this three-ports network still has characteristics of linear superposition with this new algorithm. In this threeport network, the auxiliary series voltage transformers use a two-stage structure that can further decrease measurement uncertainty. The measurement uncertainty of this proposed method at 500/√3 kV is 6.8 ppm for ratio error and 7 μrad for phase displacement ( k = 2). This new method has also been verified by comparing its results with measurement results of the PTB in Germany over the same 110/√3 kV standard voltage transformer. According to test results, the error between the two methods was less than 2.7 ppm for ratio error and 2.9 μrad for phase displacement.
- Źródło:
-
Metrology and Measurement Systems; 2022, 29, 2; 301--313
0860-8229 - Pojawia się w:
- Metrology and Measurement Systems
- Dostawca treści:
- Biblioteka Nauki