Tytuł:
Measurement accuracy verification of phasor measurement unit with dynamic phasor estimation
Autorzy:
Arendarski, B.
Rabe, S.
Heineken, W.
Komarnicki, P.
Powiązania:
https://bibliotekanauki.pl/articles/140719.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
discrete Fourier transform (DFT)
dynamic phasor
measurement accuracy
phasor measurement unit (PMU)
power system
Opis:
Power systems that are highly loaded, especially by a stochastic supply of renew- ables and the presence of storages, require dynamic measurements for their optimal control. Phasor measurement units (PMUs) can be used to capture electrical parameters of a power system. Standards on the PMU dynamic performance have been modified to incorporate their new dynamic mode of operation. This paper examines the PMU dynamic performance and proposes essential algorithms for measurement accuracy verification. Measurements of dynamic input signals, which vary in amplitude or frequency, were taken during au- tomated tests of two PMUs. The test results are presented and expounded with further recommendation for the performance requirements. This paper also presents and examines applied testing procedures with relevance to the specifications of the IEEE Standard for Synchrophasor C37.118.1™-2011 and its amendment C37.118.1a™-2014.
Źródło:
Archives of Electrical Engineering; 2018, 67, 3; 529--543
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Fir Filters Compliant with the IEEE Standard for M Class PMU
Autorzy:
Duda, K.
Zieliński, T. P.
Powiązania:
https://bibliotekanauki.pl/articles/221798.pdf
Data publikacji:
2016
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
phasor estimation
Phasor Measurement Unit
FIR filter
cosine window
flat-top window
Opis:
In this paper it is shown that M class PMU (Phasor Measurement Unit) reference model for phasor estimation recommended by the IEEE Standard C37.118.1 with the Amendment 1 is not compliant with the Standard. The reference filter preserves only the limits for TVE (total vector error), and exceeds FE (frequency error) and RFE (rate of frequency error) limits. As a remedy we propose new filters for phasor estimation for M class PMU that are fully compliant with the Standard requirements. The proposed filters are designed: 1) by the window method; 2) as flat-top windows; or as 3) optimal min-max filters. The results for all Standard compliance tests are presented, confirming good performance of the proposed filters. The proposed filters are fixed at the nominal frequency, i.e. frequency tracking and adaptive filter tuning are not required, therefore they are well suited for application in lowcost popular PMUs.
Źródło:
Metrology and Measurement Systems; 2016, 23, 4; 623-636
0860-8229
Pojawia się w:
Metrology and Measurement Systems
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Analysis of Synchrophasor Estimatioo Errors
Autorzy:
Łukowicz, M.
Cygan, S.
Powiązania:
https://bibliotekanauki.pl/articles/410593.pdf
Data publikacji:
2017
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
synchrophasor estimation
dynamic phasor
Fourier transform
Taylor Fourier series
phase locked loop
dynamic filter
Opis:
This papers discusses the analytical analysis of the syochrophasor estimation employed in electrical systems. Short time Fourier trsnsform with the phase locked loop and Taylor Fourier series are analyzed for signals relating to different states which may occor in real power systems. The object is the accurate phasor estimation regardless of the shape of input signal, what for some signal types is cumbersome. As a result of active and reactive power disturbance in a power system, the frequency deviation and amplitude fluctuations may appear in power system signals. As a consequences of short circuits or overvoltages signal changes occur. Ibis leads to unacceptable errors in short time Fourier transform resulting from Fourier transform properties. This paper presents character of occurring errors and their consequences individually for any signal deviation.
Źródło:
Present Problems of Power System Control; 2017, 8; 5-22
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Improving state estimation in smart distribution grid using synchrophasor technology: a comparison study
Autorzy:
Richter, M.
Komarnicki, P.
Hauer, I.
Powiązania:
https://bibliotekanauki.pl/articles/141592.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
accuracy analysis
case study
distribution grid state estimation
phasor measurement units
weighted least squares
Opis:
Both the growing number of dispersed generation plants and storage systems and the new roles and functions on the demand side (e.g. demand side management) are making the operation (monitoring and control) of electrical grids more complex, especially in distribution. This paper demonstrates how to integrate phasor measurements so that state estimation in a distribution grid profits optimally from the high accuracy of PMUs. Different measurement configurations consisting of conventional and synchronous mea- surement units, each with different fault tolerances for the quality of the calculated system state achieved, are analyzed and compared. Weighted least squares (WLS) algorithms for conventional, linear and hybrid state estimation provide the mathematical method used in this paper. A case study of an 18-bus test grid with real measured PMU data from a 110 kV distribution grid demonstrates the improving of the system’s state variable’s quality by using synchrophasors. The increased requirements, which are the prerequisite for the use of PMUs in the distribution grid, are identified by extensively analyzing the inaccuracy of measurement and subsequently employed to weight the measured quantities.
Źródło:
Archives of Electrical Engineering; 2018, 67, 3; 469--483
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-4 z 4

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies