Power systems that are highly loaded, especially by a stochastic supply of renew-
ables and the presence of storages, require dynamic measurements for their optimal control.
Phasor measurement units (PMUs) can be used to capture electrical parameters of a power
system. Standards on the PMU dynamic performance have been modified to incorporate
their new dynamic mode of operation. This paper examines the PMU dynamic performance
and proposes essential algorithms for measurement accuracy verification. Measurements
of dynamic input signals, which vary in amplitude or frequency, were taken during au-
tomated tests of two PMUs. The test results are presented and expounded with further
recommendation for the performance requirements. This paper also presents and examines
applied testing procedures with relevance to the specifications of the IEEE Standard for
Synchrophasor C37.118.1™-2011 and its amendment C37.118.1a™-2014.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies