Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "entropy" wg kryterium: Wszystkie pola


Wyświetlanie 1-4 z 4
Tytuł:
Maximum entropy generation rate in a heat exchanger at constant inlet parameters
Autorzy:
Laskowski, R.
Jaworski, M.
Powiązania:
https://bibliotekanauki.pl/articles/95303.pdf
Data publikacji:
2017
Wydawca:
Politechnika Koszalińska. Wydawnictwo Uczelniane
Tematy:
maximum entropy generation rate
entropy
heat exchanger
maksymalna szybkość generowania entropii
entropia
wymiennik ciepła
Opis:
The main goal of the paper is to provide a condition for which a maximum entropy generation occurs in a heat exchanger at constant inlet parameters (temperatures and mass flow rates). Knowing this condition is essential during the design of the heat exchanger as it allows designers to avoid one of its most unfavourable operating conditions in terms of thermodynamics. Entropy generation resulting from the resistance of heat-transferring fluids to flow was not taken into account. Entropy generation was analysed as a function of a heat flow rate at constant parameters at the inlet of a condenser and a counter-flow double-pipe heat exchanger. The analysis showed that for the condenser the entropy generation rate increases with the increase in the heat flow rate. The maximum entropy generation rate occurs for the maximum flow rate of the heat that can be transferred according to the definition of heat transfer effectiveness. For the counter-flow heat exchanger, the entropy generation as a function of the heat flow rate reaches maximum at constant inlet parameters (temperatures and mass flow rates). It appeared that the peak entropy generation, or the largest exergy loss, occurs when the outlet temperatures of the fluids are equal. This assertion was verified against data obtained from a simulator of the counter-flow heat exchanger for two different relations between heat capacity rates.
Źródło:
Journal of Mechanical and Energy Engineering; 2017, 1, 1; 79-86
2544-0780
2544-1671
Pojawia się w:
Journal of Mechanical and Energy Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Entropy generation in a condenser and related correlations
Autorzy:
Laskowski, R.
Jaworski, M.
Smyk, A.
Powiązania:
https://bibliotekanauki.pl/articles/240683.pdf
Data publikacji:
2015
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
steam condenser
entropy generation
kondensator pary
generowanie entropii
Opis:
The paper presents an analysis of relations describing entropy generation in a condenser of a steam unit. Connections between entropy generation, condenser ratio, and heat exchanger effectiveness, as well as relations implied by them are shown. Theoretical considerations allowed to determine limits of individual parameters which describe the condenser operation. Various relations for average temperature of the cold fluid were compared. All the proposed relations were verified against data obtained using a simulator and actual measurement data from a 200 MW unit condenser. Based on data from a simulator it was examined how the sum of entropy rates, steam condenser effectiveness, terminal temperature difference and condenser ratio vary with the change in the inlet cooling water temperature, mass flow rate of steam and the cooling water mass flow rate.
Źródło:
Archives of Thermodynamics; 2015, 36, 2; 27-48
1231-0956
2083-6023
Pojawia się w:
Archives of Thermodynamics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Estimation of a tube diameter in a ‘church window’ condenser based on entropy generation minimization
Autorzy:
Laskowski, R.
Rusowicz, A.
Grzebielec, A.
Powiązania:
https://bibliotekanauki.pl/articles/240523.pdf
Data publikacji:
2015
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
entropy generation minimization
power plant condenser
tube diameter
minimalizacja entropii generacji
skraplacz energetyczny
średnica rurek
Opis:
The internal diameter of a tube in a ‘church window’ condenser was estimated using an entropy generation minimization approach. The adopted model took into account the entropy generation due to heat transfer and flow resistance from the cooling-water side. Calculations were performed considering two equations for the flow resistance coefficient for four different roughness values of a condenser tube. Following the analysis, the internal diameter of the tube was obtained in the range of 17.5 mm to 20 mm (the current internal diameter of the condenser tube is 22 mm). The calculated diameter depends on and is positively related to the roughness assumed in the model.
Źródło:
Archives of Thermodynamics; 2015, 36, 3; 49-59
1231-0956
2083-6023
Pojawia się w:
Archives of Thermodynamics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Ocena konstrukcji skraplacza na podstawie minimum strumienia generacji entropii
The condenser design assessment on the basis of the minimum entropy generation
Autorzy:
Laskowski, R.
Rusowicz, A.
Grzebielec, A.
Jaworski, M.
Powiązania:
https://bibliotekanauki.pl/articles/271317.pdf
Data publikacji:
2016
Wydawca:
Centralny Ośrodek Badawczo-Rozwojowy Aparatury Badawczej i Dydaktycznej, COBRABiD
Tematy:
skraplacz
minimum generacji strumienia entropii
ocena konstrukcji skraplacza
condenser
minimum entropy generation
condenser design assessment
Opis:
W skraplaczach energetycznych generowane są jedne z największych strat strumienia entropii w instalacji energetycznej. Celowe jest obniżanie tej straty, aby uzyskać poprawę całkowitej sprawności instalacji. W artykule podano warunek dla minimum generacji strumienia entropii, z którego wynika, że minimum to jest osiągnięte, gdy podgrzew wody w rurkach skraplacza ma równomierny rozkład (przyjmuje taką samą wartość dla wszystkich rurek). Poprawność tego warunku sprawdzono na podstawie danych uzyskanych z symulatora 2D skraplacza dla jednego z krajowych bloków o mocy 50 MW. Na podstawie otrzymanych z symulatora przyrostów temperatur oraz odpowiadających im ciśnień pary dla 30 rurek dokonano oceny poprawności konstrukcji skraplacza.
The losses in power plants condensers are some of the biggest losses in the entropy generation in whole power plant system. It is advisable to decrease the loss for improving the overall efficiency of the system. The article presents the condition for the minimum entropy generation, which states that the minimum is achieved when the heating of the water in the tubes of the condenser has a uniform distribution (takes the same value for all tubes). The correctness of this condition was verified on the basis of data obtained from the 2D condenser simulator for one of the national units with a 50 MW electric capacity. On the basis of the simulator increases temperatures and steam pressures corresponding to 30 tubes assesses the correctness of the construction of the condenser.
Źródło:
Aparatura Badawcza i Dydaktyczna; 2016, 21, 2; 76-84
2392-1765
Pojawia się w:
Aparatura Badawcza i Dydaktyczna
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-4 z 4

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies