Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "mineral transformer oil" wg kryterium: Temat


Wyświetlanie 1-2 z 2
Tytuł:
The application of a molecular sieve for drying the insulation system of a power transformer in terms of improving its perational reliability
Autorzy:
Cybulski, Mateusz
Przybyłek, Piotr
Powiązania:
https://bibliotekanauki.pl/articles/2172034.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Polskie Naukowo-Techniczne Towarzystwo Eksploatacyjne PAN
Tematy:
power transformer
insulation system
drying
molecular sieve
mineral oil
natural ester
synthetic ester
Opis:
The first research objective was the assessment of the selectivity of water and hydrogen adsorption by the 3A molecular sieve (MS) in the terms of the safety of using the DGA (Dissolved Gas Analysis) method as a diagnostic technique. The second objective was to demonstrate the efficiency of drying the insulation system consisting of cellulose insulation impregnated with various insulating liquids in terms of improving safety and extending the service life of power transformers. In order to achieve the assumed objectives, measurement systems were prepared and material tests were carried out, based mainly on chromatographic analyzes and measurements of water content using the Karl Fischer titration method. On the basis of the obtained test results and the conducted physical analyzes, the selectivity of MS sorption was shown and it was explained that the facilitator of the adsorption of water molecules is their polar nature related to their large dipole moment. The high efficiency of drying cellulose insulation impregnated with various insulating liquids using MS was also demonstrated.
Źródło:
Eksploatacja i Niezawodność; 2022, 24, 3; 502--509
1507-2711
Pojawia się w:
Eksploatacja i Niezawodność
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Concentration analysis of gases formed in mineral oil, natural ester, and synthetic ester by discharges of high energy
Analiza stężeń gazów powstających na skutek oddziaływania łuku elektrycznego na olej mineralny oraz estry naturalne i syntetyczny
Autorzy:
Przybyłek, P.
Gielniak, J.
Powiązania:
https://bibliotekanauki.pl/articles/1365328.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Polskie Naukowo-Techniczne Towarzystwo Eksploatacyjne PAN
Tematy:
transformer
diagnostics
mineral oil
natural ester
synthetic ester
electric arc
discharge of high energy
gases
gas chromatography
transformator
diagnostyka
olej mineralny
ester naturalny
ester syntetyczny
łuk elektryczny
wyładowania zupełne
gazy
chromatografia gazowa
Opis:
The paper describes physical foundations of gases generation in different electroinsulating liquids. The authors reviewed literature concerning the analysis of gases generated in these liquids as a result of discharges of low energy. The main purpose of the research was to compare gases formed in mineral oil, natural ester, and synthetic ester resulting from discharges of high energy, which has not been studied so far. The comparison was done both in terms of gases composition and their concentration. The purpose of the research was to give an answer to the question: which of the analysed liquids ensure higher operation safety if there is a discharge of high energy in the insulating system.
W pracy opisano podstawy fizyczne związane z powstawaniem gazów w różnych cieczach elektroizolacyjnych. Dokonano przeglądu literatury dotyczącego analizy gazów generowanych w tych cieczach w wyniku wyładowań zupełnych. Głównym celem badań było porównanie gazów powstających w oleju mineralnym, estrze naturalnym oraz estrze syntetycznym w wyniku oddziaływania na te ciecze wyładowań zupełnych o bardzo dużej energii, co dotychczas nie było przedmiotem badań. Porównania dokonano zarówno pod kątem składu gazów jak i ich stężenia. Wyniki badań miały przede wszystkim dać odpowiedź na pytanie: która z analizowanych cieczy charakteryzuje się większym bezpieczeństwem eksploatacji w sytuacji wystąpienia w układzie izolacyjnym wysokoenergetycznego wyładowania zupełnego.
Źródło:
Eksploatacja i Niezawodność; 2018, 20, 3; 435-442
1507-2711
Pojawia się w:
Eksploatacja i Niezawodność
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-2 z 2

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies