Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "transmission lines" wg kryterium: Wszystkie pola


Wyświetlanie 1-6 z 6
Tytuł:
Location of arc faults on power transmission lines
Autorzy:
Pustułka, M
Iżykowski, J
Łukowicz, M
Powiązania:
https://bibliotekanauki.pl/articles/410527.pdf
Data publikacji:
2013
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
arc fault
fault location
signal processing
Opis:
This paper presents a fault location algorithm, which allows to determine the distance to a fault and fault resistance, as a result of considering natural fault loops. It is assumed that three-phase voltages and currents from both ends of the line measured asynchronously are the input signals of the fault locator. In case of the availability of synchronized measurements the elements associated with the determination of the synchronization angle should be omitted. In addition to natural fault loop signals also use of symmetrical components (positive and negative or incremental positive sequence components) to fault location were considered as well.
Źródło:
Present Problems of Power System Control; 2013, 3; s. 95-102
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Fault location in EHV transmission lines using artificial neural networks
Autorzy:
Bouthiba, T.
Powiązania:
https://bibliotekanauki.pl/articles/907284.pdf
Data publikacji:
2004
Wydawca:
Uniwersytet Zielonogórski. Oficyna Wydawnicza
Tematy:
linia przesyłowa
detekcja uszkodzeń
lokalizacja uszkodzeń
sztuczna sieć neuronowa
transmission line
fault detection
fault location
artificial neural networks
Opis:
This paper deals with the application of artificial neural networks (ANNs) to fault detection and location in extra high voltage (EHV) transmission lines for high speed protection using terminal line data. The proposed neural fault detector and locator were trained using various sets of data available from a selected power network model and simulating different fault scenarios (fault types, fault locations, fault resistances and fault inception angles) and different power system data (source capacities, source voltages, source angles, time constants of the sources). Three fault locators are proposed and a comparative study of the proposed fault locators is carried out in order to determine which ANN fault locator structure leads to the best performance. The results show that artificial neural networks offer the possibility to be used for on-line fault detection and location in transmission lines and give satisfactory results.
Źródło:
International Journal of Applied Mathematics and Computer Science; 2004, 14, 1; 69-78
1641-876X
2083-8492
Pojawia się w:
International Journal of Applied Mathematics and Computer Science
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Neural network filtration for arc faults location on power transmission lines
Autorzy:
Pustułka, M.
Iżykowski, J.
Łukowicz, M.
Powiązania:
https://bibliotekanauki.pl/articles/410589.pdf
Data publikacji:
2013
Wydawca:
Politechnika Wrocławska. Oficyna Wydawnicza Politechniki Wrocławskiej
Tematy:
arc fault
fault location
signal processing
filtration
Opis:
This paper presents filtration using neural network for arc fault location, which allows to determine the distance to a fault, as a result of considering natural fault loops. It is assumed that three-phase voltages and currents from both ends of the line are the input signals of the fault locator and naturally of the neutral network applied for filtering the input signals. In addition to natural fault loop signals also use of symmetrical components (positive and negative or incremental positive sequence components) to fault location were considered as well. Results of evaluation study have been included, analyzed and discussed. Influence of filtration has been also considered.
Źródło:
Present Problems of Power System Control; 2013, 4; 37-49
2084-2201
Pojawia się w:
Present Problems of Power System Control
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
A fault location method for hybrid transmission lines based on empirical Fourier decomposition
Autorzy:
Tao, Caixia
Xing, Baosheng
Li, Taiguo
Powiązania:
https://bibliotekanauki.pl/articles/27309957.pdf
Data publikacji:
2023
Wydawca:
Polska Akademia Nauk. Czasopisma i Monografie PAN
Tematy:
empirical Fourier decomposition
fault location
hybrid lines
Teager energy operator
traveling wave method
Opis:
This paper aims to address the problems of inaccurate location and large computation in hybrid transmission line traveling wave detection methods. In this paper, a new fault location method based on empirical Fourier decomposition (EFD) and the Teager energy operator (TEO) is proposed. Firstly, the combination of EFD and the TEO is used to detect the time difference between the arrival of the initial traveling wave of the fault at the two measurement ends of the hybrid line. Then, when the fault occurs at the midpoint of each line segment and at the connection point of the hybrid line, the time difference between the arrival of the fault traveling wave at the two measurement ends of the line is calculated according to the line parameters. By comparing the obtained time differences, it is determined whether the fault occurs in the first or second half of the line. Finally, the fault distance is calculated using the double-ended traveling wave method according to the fault section. The model was built on PSCAD and the proposed algorithm was simulated on MATLAB platform. The results demonstrate that the proposed method achieves an average fault location accuracy of 98.88% by adjusting transition resistances and fault distances and comparing with other location methods. After validation, the proposed method for locating faults has a high level of accuracy in location, computational efficiency, and reliability. It can accurately identify fault segments and locations in hybrid transmission line systems.
Źródło:
Archives of Electrical Engineering; 2023, 72, 4; 1035--1053
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Arcing Faults Location Methods for Power Transmission Lines
Metody lokalizacji zwarć łukowych w energetycznych liniach przesyłowych
Autorzy:
Pustułka, M.
Łukowicz, M.
Iżykowski, J.
Powiązania:
https://bibliotekanauki.pl/articles/396832.pdf
Data publikacji:
2014
Wydawca:
ENERGA
Tematy:
fault location
artificial neural network
arcing fault
lokalizacja zwarć
sztuczna sieć neuronowa
zwarcia łukowe
Opis:
This paper presents three different fault location approaches: one-end Takagi algorithm, two-end algorithm considering natural fault loops and neural network. It is assumed that three-phase voltages and currents from both ends of the line measured asynchronously are the input signals of the fault locator. In addition to natural fault loop signals also the use of symmetrical components (positive and negative or incremental positive sequence components) for fault location were considered. Results of the evaluation study have been included, analyzed and discussed. The impact of filtration has also been considered.
W artykule przedstawiono trzy metody lokalizacji zwarć: algorytm Takagi, algorytm wykorzystujący pomiary z dwóch końców linii oraz algorytm z siecią neuronową. Do lokalizacji zwarcia w algorytmach użyto napięcia i prądów mierzonych z obu końców linii. Sieć neuronowa wspomagana była rozwiązaniem uzyskanym za pomocą algorytmu, który w celu określenia miejsca zwarcia, oprócz naturalnych sygnałów pętli zwarciowych, wykorzystywał również sygnały składowych symetrycznych. Przeanalizowany został wpływ filtracji sygnałów zasilających na dokładność algorytmów.
Źródło:
Acta Energetica; 2014, 1; 142-151
2300-3022
Pojawia się w:
Acta Energetica
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Metody lokalizacji zwarć łukowych w energetycznych liniach przesyłowych
Arcing faults location methods for power transmission lines logic
Autorzy:
Pustułka, M.
Łukowicz, M.
Iżykowski, J.
Powiązania:
https://bibliotekanauki.pl/articles/267653.pdf
Data publikacji:
2013
Wydawca:
Politechnika Gdańska. Wydział Elektrotechniki i Automatyki
Tematy:
lokalizacja zwarć
sztuczna sieć neuronowa
fault location
artificial neural network
arcing fault
Opis:
W artykule przedstawiono trzy metody lokalizacji zwarć: algorytm Takagi, algorytm wykorzystujący pomiary z dwóch końców linii oraz algorytm z siecią neuronową. Do lokalizacji zwarcia w algorytmach wykorzystano napięcia i prądy mierzone z obu końców linii. Sieć neuronowa wspomagana była rozwiązaniem uzyskanym za pomocą algorytmu, który w celu określenia miejsca zwarcia oprócz naturalnych sygnałów pętli zwarciowych wykorzystywał również sygnały składowych symetrycznych.
This paper presents a three different fault location approaches: one-end Takagi algorithm, two-end algorithm considering natural fault loops and neural network. It is assumed that three-phase voltages and currents from both ends of the line measured asynchronously are the input signals of the fault locator. In addition to natural fault loop signals also the use of symmetrical components (positive and negative or incremental positive sequence components) for fault location were considered. Results of evaluation study have been included, analyzed and discussed. Impact of filtration has been considered as well.
Źródło:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej; 2013, 32; 103-106
1425-5766
2353-1290
Pojawia się w:
Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-6 z 6

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies