Tytuł:
Analysis of the neutral grounding modes influence on the reliability characteristics of local systems with renewable energy sources
Autorzy:
Ostapchuk, Oleksandr
Kuznetsov, Valeriy
Kruczek, Włodzimierz
Kuznetsov, Vitaliy
Tsyplenkov, Dmytro
Powiązania:
https://bibliotekanauki.pl/articles/1840882.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Polskie Towarzystwo Diagnostyki Technicznej PAN
Tematy:
electric networks
protection
reliability
ground failure current
electrical safety
system with isolated neutral
system with resonant grounding
system with low-impedance neutral grounding
sieć elektryczna
ochrona
niezawodność
bezpieczeństwo
Opis:
When comparing the performance indicators of electrical networks with different types of neutral grounding, along with the fulfilment of the requirement to ensure reliability of power supply to consumers, serious attention is drawn to the main network parameters influencing the performance of power supply systems. Analysis of research and its results, reported above, on the influence of the neutral ground of power networks on the reliability and electrical safety conditions of the power supply systems as a whole, on the damage of distribution networks and electrical equipment as well as on the working capacity of relay protection devices, provides an opportunity to estimate each specific operation mode of the neutral and to develop recommendations aimed at strengthening the positive indicators of the corresponding modes. Other things being equal, reliability of power supply to electrical receivers or reliability of distribution networks is mainly determined by the damage to network elements and the performance of relay protection devices. The degree of influence of these factors on the reliability of distribution networks depends on the neutral mode, which in turn determines the level of internal overvoltages and the nature of transient processes at earth fault.
Źródło:
Diagnostyka; 2021, 22, 1; 45-56
1641-6414
2449-5220
Pojawia się w:
Diagnostyka
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Quick-response protection system against electric shock in distributed generation systems
Autorzy:
Shkrabets, Fedir
Plaksin, Sergej
Ostapchuk, Oleksandr
Kuznetsov, Valeriy
Tymchenko, Irina
Muntian, Antonina
Powiązania:
https://bibliotekanauki.pl/articles/1840853.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Polskie Towarzystwo Diagnostyki Technicznej PAN
Tematy:
electric networks
protection
reliability
ground fault current
electrical safety
protection against electric shock
signal processing system
analog filtering
sieci elektryczne
ochrona
niezawodność
bezpieczeństwo elektryczne
ochrona przeciwporażeniowa
system przetwarzania sygnału
filtracja analogowa
Opis:
The peculiarities of the operation of distributed generation systems lead to a change in the requirements for the reliability and safety of the power distribution systems in which they are integrated. To meet the increased requirements, continuous monitoring of the insulation parameters (active resistance and capacitance to ground) is often used with operating artificial non-industrial frequency operational signals introduced into the network. In the case of a sudden touch, such a system is not effective, since the response time of the protection device, which consists of the signal processing time and the operating of the actuator, is crucially important. For the used operational signals with a frequency of 100 and 200 Hz, the processing time using the Fourier transform is 10 ms for 100 Hz and 5 ms for 200 Hz. Considering that the response time of the fastest actuators (based on vacuum switches) is from 3 to 7 ms, this is a rather significant period of time. To develop an effective resolver system, the capabilities of the Matlab environment were used to determine the most successful design of an analog prototype (Butterworth, Bessel, Chebyshev and Cauer of 6th order) for an operational signal with a frequency of 200 Hz. As a result, the processing time was established, which varies widely from 3.5 to 19 ms. Taking into account the known indicators, namely the frequency and number of operational signals, a signal processing system was developed using the vector-matrix analysis method. As a result of modeling the processing characteristics of functional signals (at a sampling rate of 1 kHz), the system quick-response was 3 ms, with the possibility of its further decrease as its productiveness increases.
Źródło:
Diagnostyka; 2021, 22, 3; 59-65
1641-6414
2449-5220
Pojawia się w:
Diagnostyka
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Quick-response protection system against electric shock in distributed generation systems
Autorzy:
Shkrabets, Fedir
Plaksin, Sergej
Ostapchuk, Oleksandr
Kuznetsov, Valeriy
Tymchenko, Irina
Muntian, Antonina
Powiązania:
https://bibliotekanauki.pl/articles/1840876.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Polskie Towarzystwo Diagnostyki Technicznej PAN
Tematy:
electric networks
protection
reliability
ground fault current
electrical safety
protection against electric shock
signal processing system
analog filtering
sieci elektryczne
ochrona
niezawodność
bezpieczeństwo elektryczne
ochrona przeciwporażeniowa
system przetwarzania sygnału
filtracja analogowa
Opis:
The peculiarities of the operation of distributed generation systems lead to a change in the requirements for the reliability and safety of the power distribution systems in which they are integrated. To meet the increased requirements, continuous monitoring of the insulation parameters (active resistance and capacitance to ground) is often used with operating artificial non-industrial frequency operational signals introduced into the network. In the case of a sudden touch, such a system is not effective, since the response time of the protection device, which consists of the signal processing time and the operating of the actuator, is crucially important. For the used operational signals with a frequency of 100 and 200 Hz, the processing time using the Fourier transform is 10 ms for 100 Hz and 5 ms for 200 Hz. Considering that the response time of the fastest actuators (based on vacuum switches) is from 3 to 7 ms, this is a rather significant period of time. To develop an effective resolver system, the capabilities of the Matlab environment were used to determine the most successful design of an analog prototype (Butterworth, Bessel, Chebyshev and Cauer of 6th order) for an operational signal with a frequency of 200 Hz. As a result, the processing time was established, which varies widely from 3.5 to 19 ms. Taking into account the known indicators, namely the frequency and number of operational signals, a signal processing system was developed using the vector-matrix analysis method. As a result of modeling the processing characteristics of functional signals (at a sampling rate of 1 kHz), the system quick-response was 3 ms, with the possibility of its further decrease as its productiveness increases.
Źródło:
Diagnostyka; 2021, 22, 3; 59-65
1641-6414
2449-5220
Pojawia się w:
Diagnostyka
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-3 z 3

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies