Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "electric strength" wg kryterium: Temat


Wyświetlanie 1-5 z 5
Tytuł:
Methodology for testing the electric strength of vacuum chambers designed for modern medium voltage switchgear
Autorzy:
Węgierek, Paweł
Lech, Michał
Kozak, Czesław
Pastuszak, Justyna
Powiązania:
https://bibliotekanauki.pl/articles/1849145.pdf
Data publikacji:
2020
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
vacuum interrupter
vacuum breakdown
electric strength
vacuum switchgear
measurement uncertainty
Opis:
The article presents methodology for testing the electric strength of vacuum chambers designed for modern medium voltage switchgear developed by the authors, using two innovative test stands designed and constructed by the research team above. Verification of the correctness of operation of the test stands, as well as the validity of the developed methodology was carried out by performing a series of tests. It was determined that below certain pressure values in the tested chamber (from about 5:0 x 100 Pa for station 1 and for about 4:0 x 10-1 Pa for station 2), the electric strength maintains a constant value, which guarantees stable operation of the vacuum chamber. The values of the total measurement uncertainty for the electric strength tests were also estimated.
Źródło:
Metrology and Measurement Systems; 2020, 27, 4; 687-700
0860-8229
Pojawia się w:
Metrology and Measurement Systems
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Sulphur hexafluoride as a high-voltage insulation - selected problems
Autorzy:
Opydo, W.
Juszczyk, Z.
Stawicki, J.
Opydo-Szymaczek, J.
Powiązania:
https://bibliotekanauki.pl/articles/97179.pdf
Data publikacji:
2014
Wydawca:
Politechnika Poznańska. Wydawnictwo Politechniki Poznańskiej
Tematy:
high-voltage insulation
electric strength
sulphur hexafluoride (SF6)
toxic byproducts
Opis:
The paper presents some selected properties of sulphur hexafluoride (SF6) a medium used for high-voltage insulation and electric arc suppression purposes. The results are presented of the studies aimed at determining the effect of the electrode material type, temperature, gas density and interelectrode gap on the SF6 electric strength. The considered systems had both flat electrodes or one flat and the other (cathode) having the form of a rod of 3 mm or 30 mm diameter, ended with a hemisphere. The electrodes have been made of stainless steel or aluminum. The results were mathematically processed with the use of the Statistica [11] computer software. It was found that SF6 temperature changes in the range from 243 K to 293 K with constant SF6 density did not cause variation of electric strength of the gas. Moreover, the effect of the electrode material type on electric strength of SF6 was observed only in the systems distinguished by macroscopic uniformity of the electric field and in case of the gas density exceeding 15 kg/m3, corresponding to SF6 pressure amounting about to 2.5-105 Pa in the temperature 293 K. Physical interpretation of the study results is proposed and formulated. Additionally, the paper discusses the hazards arising from the use of SF6 for the health of the persons operating the equipment and for the environment.
Źródło:
Computer Applications in Electrical Engineering; 2014, 12; 206-216
1508-4248
Pojawia się w:
Computer Applications in Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Review and comparison of electro-insulation properties of vacuum and sulphur hexafluoride
Autorzy:
Opydo, W.
Stawicki, J.
Opydo-Szymaczek, J.
Powiązania:
https://bibliotekanauki.pl/articles/97567.pdf
Data publikacji:
2013
Wydawca:
Politechnika Poznańska. Wydawnictwo Politechniki Poznańskiej
Tematy:
high-voltage insulation
electric strength
vacuum
sulphur hexafluoride
SF6
toxic byproducts
Opis:
The paper specifies the results of the tests on electric strength of vacuum, sulphur hexafluoride (SF6) and the insulation mineral oil under alternate voltage. The tests have been carried out for planar electrodes made of stainless steel or aluminum. It was found that 10-3 Pa vacuum, 3 105 Pa SF6, and insulation mineral oil situated with equal inter-electrode gap equal to several millimeters, have approximately equal electric strength. The degrees of influence of basic parameters of the insulation system on electric strength of SF6 and vacuum are presented. Advantages and faults of vacuum, SF6, and insulation mineral oil are mentioned, taking into account possible use of these media as a high-voltage insulation in various electric equipment. Mathematical processing of the test results was carried out with the use of the Statistica software [5].
Źródło:
Computer Applications in Electrical Engineering; 2013, 11; 222-229
1508-4248
Pojawia się w:
Computer Applications in Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
The impulse characteristics and electric strength of varistors piles depend on geometry of the electrodes
Charatkerystyki impulsowe i wytrzymałość elektryczna stosów warystorowych w zależności od geometrii elektrod
Autorzy:
Kogut, K.
Kasprzyk, K.
Zboromirska–Wnukiewicz, B.
Powiązania:
https://bibliotekanauki.pl/articles/407889.pdf
Data publikacji:
2014
Wydawca:
Politechnika Lubelska. Wydawnictwo Politechniki Lubelskiej
Tematy:
varistors
surface discharge
electric strength
flashover voltage
warystory
wyładowanie powierzchniowe
wytrzymałość elektryczna
napięcie przeskoku
Opis:
The paper describes the results of the impulse characteristics and electric strength measurements of the pile of varistors with modified side surface. Basing on the impulse voltage tests on the surge arresters it was found that one of the reasons of the failures of these devices may be the surface discharge at the varistor - insulating housing phase boundary, through the gas between them. Flashover voltage of power protecting systems can be increase by applying of semi – conducting covers which will carry away the generated surface charge and uniform the distribution of electric field on material surface. Comparing two types of electrodes configuration on varistors, it was found that systems without gap between electrode and side surface of varistor exhibited higher values of withstanding voltage whether their side surfaces were covered or not covered with insulating or semiconducting layer.
W pracy wyznaczono charakterystyki impulsowe oraz wytrzymałość stosów warystorowych o modyfikowanej powierzchni bocznej. Na podstawie wyników pomiarów przy napięciu impulsowym na ogranicznikach przepięć stwierdzono, że przyczyną ich uszkodzeń może być wyładowanie powierzchniowe rozwijające się w szczelinie powietrznej na granicy faz warystor – osłona izolacyjna. Napięcie przeskoku można zwiększyć poprzez zastosowanie warstw półprzewodzących, umożliwiających odprowadzenie ładunku powierzchniowego i wyrównanie rozkładu pola elektrycznego na powierzchni materiału. Na podstawie porównania dwóch konfiguracji elektrod warystorów stwierdzono, że układ bez odstępu pomiędzy elektrodą a powierzchnią boczną warystora posiada wyższą wytrzymałość napięciową niezależnie od modyfikacji powierzchni bocznej.
Źródło:
Informatyka, Automatyka, Pomiary w Gospodarce i Ochronie Środowiska; 2014, 3; 6-9
2083-0157
2391-6761
Pojawia się w:
Informatyka, Automatyka, Pomiary w Gospodarce i Ochronie Środowiska
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Disassemblable vacuum chamber as an innovative test stand designed for research on improving the operational parametersof power switching apparatus
Rozbieralna komora próżniowa jako innowacyjne stanowisko badawcze przeznaczone do badań nad poprawą parametrów eksploatacyjnych elektroenergetycznej aparatury łączeniowej
Autorzy:
Lech, Michał
Powiązania:
https://bibliotekanauki.pl/articles/1841307.pdf
Data publikacji:
2020
Wydawca:
Politechnika Lubelska. Wydawnictwo Politechniki Lubelskiej
Tematy:
vacuum breakdown
vacuum switchgears
vacuum technology
electric strength
przebicie elektryczne w próżni
próżniowa aparatura łączeniowa
technologia próżniowa
wytrzymałość elektryczna
Opis:
The Polish power industry is characterized by outdated elements and is in poor technical condition. This applies mainly to overhead lines operating at medium and high voltage (MV and HV) levels. Moreover, the Energy Regulatory Office (ERO) requires the Distribution System Operatorsto supply electricity with specified parameters, ensuring uninterrupted electricity supply to end users. Failure to meet these conditions results in specific financial penalties. In connection with the above, there is a strong need to upgrade the existing electricity grids using modern equipment. The article presents an innovative, original research position based on the so-called dismountable vacuum chamber, which allows research to be conductedon improving the performance of modern switching equipment used in Smart Grid networks. The article also presents the resultsof electric strength tests of the inter-contact break inorder to confirm the correctness of operation of the described test stand.
Polska elektroenergetyka cechuje się elementami przestarzałymi oraz w złej kondycji technicznej. Dotyczy to przede wszystkim linii napowietrznych pracujących na poziomie średnich i wysokich napięć (SN i WN). Co więcej, Urząd Regulacji Energetyki (URE) wymaga od Operatorów Systemu Dystrybucyjnego dostarczania energii elektrycznej o określonych parametrach, zapewniających odbiorcom końcowym bezprzerwowe dostawy energii elektrycznej. Niespełnienie tych warunków skutkuje określonymi karami finansowymi. W związku z powyższym istnieje silna potrzeba modernizacji istniejących sieci elektroenergetycznych z wykorzystaniem nowoczesnej aparatury. W artykule przedstawiono innowacyjne, autorskie stanowisko badawcze oparte o tzw. rozbieralną komorę próżniową, które umożliwia przeprowadzenie badań nad poprawą parametrów eksploatacyjnych nowoczesnej aparatury łączeniowej wykorzystywanej w sieciach Smart Grid. Przedstawiono również wyniki badań wytrzymałości elektrycznej przerwy międzystykowej celem potwierdzenia poprawności działania opisanego stanowiska badawczego.
Źródło:
Informatyka, Automatyka, Pomiary w Gospodarce i Ochronie Środowiska; 2020, 10, 3; 66-69
2083-0157
2391-6761
Pojawia się w:
Informatyka, Automatyka, Pomiary w Gospodarce i Ochronie Środowiska
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-5 z 5

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies