- Tytuł:
-
Uszkodzenia izolatora przepustowego i awaria transformatora
Damage of the bushing insulator and the transformer’s breakdown - Autorzy:
-
Glinka, T.
Drak, B.
Kapinos, J. - Powiązania:
- https://bibliotekanauki.pl/articles/1367805.pdf
- Data publikacji:
- 2015
- Wydawca:
- Sieć Badawcza Łukasiewicz - Instytut Napędów i Maszyn Elektrycznych Komel
- Tematy:
-
izolatory przepustowe papierowo-olejowe
transformatory energetyczne
awaria izolatorów
pożar transformatorów
paper-oil bushing insulators
power transformers
insulators breakdown
transformers fire - Opis:
-
This article presents two examples of the fire in transformers, caused by the 400 kV and 220 kV paper-oil-type insulators breakdown. The bushing insulators’ breakdown was caused by the partial discharges insi de of the paper insulation, which leaded to insulator’s explosion, phase short-circuit fault and also to fire of the transformers. An example is also shown in this article of the power transformer with dry-type bushing insulators, which seems to be safer in the exploitation.
W artykule przedstawiono dwa przykłady pożaru transformatorów spowodowane awarią izolatorów przepustowych papierowo-olejowych 400 kV i 220 kV. Przyczyną uszkodzenia izolatorów przepustowych były wyładowania niezupełne wewnątrz izolacji papierowej, które doprowadziły do eksplozji izolatora, zwarcia fazowego i pożaru transformatorów. Przedstawiono przykład transformatora z izolatorami przepustowymi suchymi, które wydają się być bardziej bezpieczne w eksploatacji. - Źródło:
-
Maszyny Elektryczne: zeszyty problemowe; 2015, 2, 106; 135-140
0239-3646
2084-5618 - Pojawia się w:
- Maszyny Elektryczne: zeszyty problemowe
- Dostawca treści:
- Biblioteka Nauki