Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "Boczar, T." wg kryterium: Autor


Wyświetlanie 1-2 z 2
Tytuł:
The Wavelet Analysis of the Vibroacoustic Signal Measurement in a Transient State Operation of Power Transformer
Autorzy:
Borucki, S.
Cichon, A.
Boczar, T.
Zmarzly, D.
Powiązania:
https://bibliotekanauki.pl/articles/1417934.pdf
Data publikacji:
2012-11
Wydawca:
Polska Akademia Nauk. Instytut Fizyki PAN
Tematy:
43.40.-r
43.40.Vn
43.58.Wc
Opis:
The article presents the results of attempts made to develop a non-invasive diagnostic method of a technical state of a transformer's core based on an analysis of mechanical vibrations registered during the start-up of the transformer analyzed. The paper presents a characteristic of the transformer under study, the measuring systems applied and the method developed for assessing the degree of the core loosening. The original results presented in the paper have been obtained under laboratory conditions during tests conducted on an oil transformer of 200 kVA. The analysis of recorded virboacoustic signals was performed by means of discrete wavelet transform for three different operating cases: the transformer with no core defect, the transformer with loose screws of the magnetic circuit of the upper yoke, and the transformer with completely loosen screws of the beam of the upper yoke and the lower core. The signals have been recorded on two perpendicular measuring axes: 0X and 0Y and their measured values were subject to the wavelet analysis.
Źródło:
Acta Physica Polonica A; 2012, 122, 5; 800-803
0587-4246
1898-794X
Pojawia się w:
Acta Physica Polonica A
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
The Critical Evaluation of the Vibroacoustic Criteria Used in Poland to Diagnose of Power Transformer Cores
Autorzy:
Borucki, S.
Cichon, A.
Boczar, T.
Zmarzly, D.
Powiązania:
https://bibliotekanauki.pl/articles/1399335.pdf
Data publikacji:
2013-09
Wydawca:
Polska Akademia Nauk. Instytut Fizyki PAN
Tematy:
43.40.-r
43.40.Vn
43.58.Wc
Opis:
The subject matter of this article concerns the diagnostic test results of transformer cores by measuring and analysing vibroacoustic signals registered during their normal operation. The main objective of this research study conducted by the authors, the results of which are published in this paper, is a critical analysis of vibroacoustic criteria, which are adopted in Poland nowadays, and based on which, the assessment of the core technical condition is performed. This article presents exemplary results that were obtained on two twin units of type TET 8509 with a power of 40 MVA. The paper specifies diagnosed structures, the measurement system applied, and the currently used methodology to assess the degree of core loosening. To determine the efficacy and assessment accuracy of the applied vibroacoustic criteria, correlation between mechanical vibration measurements of the tested transformer tanks and results obtained by gas chromatography was performed.
Źródło:
Acta Physica Polonica A; 2013, 124, 3; 391-394
0587-4246
1898-794X
Pojawia się w:
Acta Physica Polonica A
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-2 z 2

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies