Application of a Phase Resolved Partial Discharge Pattern Analysis for Acoustic Emission Method in High Voltage Insulation Systems Diagnostics
Autorzy:
Kunicki, M.
Cichoń, A.
Powiązania:
https://bibliotekanauki.pl/articles/177912.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
acoustic emission
partial discharge
transformer diagnostics
insulation system
Opis:
An alternative method for analysis of acoustic emission (AE) signals generated by partial discharges (PD), based on a correlation between voltage phase run and AE pulses, so called phase resolved PD pattern (PRPD), is presented in the paper. PRPD pattern is a well-known analysis tool commonly used in such PD diagnostic methods as conventional electrical and UHF ones. Moreover, it yields various signal analysis abilities and allows a direct correlation indication between measurement results achieved using different methods. An original PRPD measurement methodology applied for AE method as well as some exemplary measurement results and further data analysis capabilities are presented in the paper. Also a comparative analysis of PRPD patterns achieved using various measurement methods and different PD source configurations have been investigated. All presented experiments were done under laboratory conditions using PD model sources immersed in the insulation oil. The main purpose of the presented research is to indicate an all-embracing analytical tool that yields an ability to direct comparison (qualitative as well as quantitative) of the AE measurement results with other commonly applied PD measurement methods. The presented results give a solid fundamental for further research work concerning a direct correlation method for AE and other described in the paper diagnostic techniques, mainly in order to continue PD phenomena analysis and assessment in real life high voltage apparatus insulation systems under normal onsite operation conditions.
Źródło:
Archives of Acoustics; 2018, 43, 2; 235-243
0137-5075
Pojawia się w:
Archives of Acoustics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Comparison of concentrated winding topologies considering transient voltages in the winding system of inverter-driven low-voltage machines
Autorzy:
Pauli, Florian
Driendl, Niklas
Mönninghoff, Sebastian
Hameyer, Kay
Powiązania:
https://bibliotekanauki.pl/articles/2172796.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
d/d
electrical machines
insulation system
inverters
transient voltages
Opis:
To reduce the losses of the power electronic inverter, the voltage slew rate (d u/d t) of the electric motors supplying voltage is increasing. As steep voltage slopes excite high frequencies in the megahertz range, transient phenomena in the winding of the electrical machine occur. To design the insulation system, the maximum electric potential difference between the conducting elements must be predicted. General design rules can lead to a significant overengineering of the interturn insulation, particularly when considering smaller stators with a known wire distribution. Therefore, two different winding topologies are studied comparing the voltage distribution in a round-wire winding and a winding with preformed coils.
Źródło:
Archives of Electrical Engineering; 2022, 71, 4; 865--880
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Influence of conductive particle contaminationon the insulation system of rotating electrical machines with direct oil cooling
Autorzy:
Yang, Liguo
Pauli, Florian
Zhang, Shimin
Hambrecht, Fabian
Hameyer, Kay
Powiązania:
https://bibliotekanauki.pl/articles/2135735.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
cooling
insulation system
particle contamination
partial discharge
surface resistance
Opis:
An integration of the electrical machine and the gearbox is attracting particular attention for the design of modern electric and hybrid drive trains, since it saves overall space and subsequently increases the power density. Another benefit of a high level of integration is that it enables a combined application of oils as both cooling fluid for the electrical machine and as lubrication fluid for the transmission system. In this way, the power density of the integrated drive train can be further increased. During the oil cycling, conductive contaminations may be introduced and subsequently have an influence on the function of the insulation system of the electrical machine. In the present work, the influences of the cooling oil and its conductive contaminations, conductive particles as well as their combination with humidity, on the electrical and dielectric properties of the insulation system are studied. The results show that by application of the cooling oil, the partial discharge inception voltage (PDIV) of the winding insulation increases significantly so that an electrical breakdown is prone to happen before a partial discharge (PD) occurs. With increasing particle contamination, the PDIV of the insulation system decreases significantly, while the capacitance increases. Besides, conductive particles and humidity decrease the surface resistance and surface breakdown voltage of the insulation papers significantly. The results indicate that the conductive particle contaminations can play an important role for the electrical degradation of the insulation system.
Źródło:
Archives of Electrical Engineering; 2022, 71, 3; 789--804
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Low voltage winding insulation systems under the influence of high du/dt slew rate inverter voltage
Autorzy:
Pauli, Florian
Ruf, Andreas
Hameyer, Kay
Powiązania:
https://bibliotekanauki.pl/articles/140993.pdf
Data publikacji:
2020
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
life time
partial discharge
SiC semiconductors
winding insulation system
Opis:
Variable speed and low voltage electrical drives are commonly operated by frequency converters. According to recent developments, there is a trend in the area of semi-conductors, that switching frequency and voltage slew rate will increase significantly. The aim of these semiconductors is to reduce the switching losses and to increase the switching frequency, which enables to reduce the size of passive components in the powerelectric circuit. This results in less material effort and lower cost, for the power electronic component. However, electric motors operated by high slew rate inverters show problems in the winding insulation, which have to be analyzed. Such problems are well known for high voltage machines. Due to the increasing slew rate, this problematic occurs in low voltage machines nowadays as well. Here, the influence of fast switching semiconductors on the winding insulation system is studied, using accelerated ageing tests with fast switching high-voltage generators.
Źródło:
Archives of Electrical Engineering; 2020, 69, 1; 187-202
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
High voltage harmonics induced modifications of PD phase-resolved patterns
Autorzy:
Florkowski, M.
Florkowska, B.
Zydroń, P.
Powiązania:
https://bibliotekanauki.pl/articles/141372.pdf
Data publikacji:
2018
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
electrical insulation system
diagnostics
harmonics
partial discharges
phase-resolved patterns
Opis:
Partial discharges (PD) are influencing electrical insulating systems of high voltage electrical devices. Typically, in laboratory and diagnostics AC tests focused on measuring and analysis of PD, a pure sinusoidal voltage waveform is assumed. However, in practice the spectral content of the working voltage is rarely so ideal and additional spectral components have a significant impact on the discharge behaviour in electrical insulation systems. In this paper the influence of voltage harmonics on PD behaviour and phase-resolved PD patterns evolution is analysed. The presented experiments were conducted on a specimen representing a gaseous inclusion embedded in electrical insulation. The experimental results showed that various harmonic compositions superimposed on the fundamental sinusoidal waveform have a significant impact on PD intensity and maximum charge. In consequence, the derived patterns of PD phase, and magnitude distributions are distorted, and statistical parameters calculated on their basis are changed. In certain environments, neglecting harmonic content in the testing voltage may lead to a misleading interpretation and assessment of PD severity.
Źródło:
Archives of Electrical Engineering; 2018, 67, 2; 231--246
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Influence of thermal-mechanical stress on the insulation system of a low voltage electrical machine
Autorzy:
Yang, Liguo
Pauli, Florian
Hameyer, Kay
Powiązania:
https://bibliotekanauki.pl/articles/1841343.pdf
Data publikacji:
2021
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
insulation system
material fatigue
thermal-mechanical stress
system izolacji
zmęczenie materiału
naprężenie cieplno-mechaniczne
Opis:
Varying ohmic loss in the winding of electrical machines, which are operated atvarious operating points, results in temperature changes during operation. Particularly, when the temperature is varying dynamically, the insulation system suffers from repeated thermal-mechanical stress, since the thermal expansion coefficients of the insulating materials and copper conductors are different. For the appropriate design of an insulation system, the effect of thermal-mechanical stress must be known. In the present work, motorettes are subjected to repeated thermal cycles. The expected lifetime is estimated and compared to the life time which is achieved by applying a lifetime-model which only considers thermal aging while ignoring thermal-mechanical stress effects. In addition, the hotspot temperature is simulated, the lifetime at the hotspot is estimated as the worst case. As expected, the results indicate that the thermal-mechanical stress plays a significant role during dynamic thermal aging of the winding insulation system. To better understand the thermal-mechanical stress effect, the resulting thermal-mechanical stress in a single wire is analyzed by the finite element method. A preliminary analysis of the aging mechanism of materials due to cyclic thermal-mechanical stress is performed with the theory of material fatigue.
Źródło:
Archives of Electrical Engineering; 2021, 70, 1; 233-244
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-6 z 6

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies