- Tytuł:
- Study of the impact of 220 kV SISFCL on the distance protection for transmission line
- Autorzy:
-
Luo, Y.
Shi, T.
Huang, L. - Powiązania:
- https://bibliotekanauki.pl/articles/141728.pdf
- Data publikacji:
- 2018
- Wydawca:
- Polska Akademia Nauk. Czytelnia Czasopism PAN
- Tematy:
-
SISFCL
distance protection
EMTDC/PSCAD
220 kV transmission line
setting method - Opis:
- As the most typical application of superconducting technology, the Saturated Iron core Superconducting Fault Current Limiter (SISFCL) is a kind of ideal high voltage limiter, which can achieve noticeable limiting endless stream and has wide application prospect. However, the selectivity and sensitivity of the distance protection (DP) in the high voltage transmission network would be affected by the impedance characteristics of SISFCL. For these problems, firstly the structure and the working principle of the SISFCL are introduced briefly. Secondly, the impact mechanisms of 220 kV SISFCL on the original distance protection for the transmission line (TL) are analyzed. Then two methods of eliminating influences are deduced from the previous analysis and an improved setting method based on SISFCL for distance protection is proposed. Finally, we used EMTDC/PSCAD software to build the 220 kV SISFCL and distance protection model in the transmission network. The simulation results demonstrate that the proposed setting strategy can effectively improve the selectivity and sensitivity of distance protection and provide a reference for the practical applications of SISFCL applied to the transmission line.
- Źródło:
-
Archives of Electrical Engineering; 2018, 67, 1; 151-163
1427-4221
2300-2506 - Pojawia się w:
- Archives of Electrical Engineering
- Dostawca treści:
- Biblioteka Nauki