Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "power active filter" wg kryterium: Temat


Wyświetlanie 1-5 z 5
Tytuł:
Control circuit for series active power filters based on programmable logic devices
Autorzy:
Supronowicz, H.
Olszewski, A.
Gawiński, H.
Powiązania:
https://bibliotekanauki.pl/articles/262739.pdf
Data publikacji:
2006
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
power electronics
active power filter
power quality
Opis:
This paper describes a control circuit for the active power filters working with three-phase AC power line. It describes logic circuitries as well as laboratory test results. The control circuit was realized with programmable logic devices, fast analog-to-digital and digital-to-analog converters. Proposed system working with open-loop control, it allows significantly simplifying its logic structure. Programmable logic devices do simultaneously a few independent tasks, so a control algorithm can be performing fast, improving considerably compensation dynamic. This paper includes results of laboratory tests of the active power filter consisted of proposed control circuit and a voltage-source converter.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2006, 12, 2; 21-25
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Single-phase power active filter using instantaneous reactive power theory : theoretical and practical approach
Autorzy:
Altus, J.
Michalik, J.
Dobrucky, B.
Viet, L. H.
Powiązania:
https://bibliotekanauki.pl/articles/262653.pdf
Data publikacji:
2005
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
power active filter
p-q power theory
orthogonal transformations
single-phase system
fictitous virtual quantity
Opis:
The paper deals with the new method of analysis, synthesis and experimentation of single-phase power active filters. By using a new particular transformation theory, the ordinary single-phase system can be transformed into an equivalent two-axes orthogonal one. The new original thought is based on the idea that ordinary single-phase quantity can be complemented bv fictitious second phase so that both of them will create an orthogonal system, as is usual in three-phase systems, in spite of [1]. Application of the above theory makes it possible to use complex methods of analysis as the instantaneous reactive power method, which have not been usable for single-phase systems so far. Both, the active and reactive powers can be determined by this way. Practical application of the method is outlined for the case of reference current determination for single-phase power active filter. The paper shows some examples of the simu-lution verification results, which proved a high accuracy and extremely fast response of the single-phase active filter with control, based on the introduced method. The effectiveness of proposed control algorithm is also demonstrated by experimental results, which were carried out on the single - phase active parallel filter, power rate of 25 kVA and controlled by 32 - bit Heating point digital signal processor TMS 320C31.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2005, 11, 1; 33-38
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Sampled Method of Active Power Filter Control. Part II
Autorzy:
Szromba, A.
Powiązania:
https://bibliotekanauki.pl/articles/262604.pdf
Data publikacji:
2006
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
shunt active power filter
power factor
power quality
Opis:
The aim of the paper is to demonstrate how to use sampled method of control of a shunt active power filter to maintain invariable power of a supplying voltage source, even though the supplied load varies randomly. The definition by S. Fryze of load current components is used as a basis for the construction of a family of shunt active power filters. The distinctive property of these filters is maintaining non-deformed source current in every one individually considered period T. The main features of the family of filters are described in the first part of the paper, which is devoted to DC circuit. In the second part, the results are implemented to a single- and a three-phase circuit. Additionally, some new features, which may be applied only for AC circuit, are discussed in the second part. All the presented waveforms are obtained using computer simulation tools.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2006, 12, 1; 29-39
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Sampled method of active power filter control. Part 1
Autorzy:
Szromba, A.
Powiązania:
https://bibliotekanauki.pl/articles/262771.pdf
Data publikacji:
2005
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
shunt active power filter
power factor
power quality
Opis:
The aim of the paper is to demonstrate how to use sampled method of control of a shunt active power filter to maintain invariable power of a supplying voltage source, even though the supplied load varies randomly. The definition by S. Fryze of load current components is used as a basis for the construction of a family of shunt active power filters. The under discussion family of filters is designed to work synchronically with a time period T. The period T may be regulated in some range. The distinctive property of these filters is maintaining non-deformed source current in every one individually considered period T. Main features of the family of filters are described in the first part of the paper, which is devoted to DC circuit. Then in the second part, the results, which are obtained in DC circuit, are implemented to a single- and then to a three-phase circuit. Additionally, some new features, which may be applied only for AC circuit, are discussed in the second part. All the presented waveforms are obtained using computer simulation tools.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2005, 11, 2; 91-98
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Currents physical components theory and p-q power theory in the control of the three-phase shunt active power filter
Autorzy:
Firlit, A.
Powiązania:
https://bibliotekanauki.pl/articles/262629.pdf
Data publikacji:
2007
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
active power filter
power theory
p-q power theory
CPC power theory
switching compensators
electric power quality
Opis:
This paper presents the comparison among the control algorithms of a three phase, three wire shunt active power filter. The control algorithms are based on: 1) the current's physical components theory, 2) the p-q power theory. The active power filter operation under the distorted supply voltage at the point of common coupling condition is considered. The comparison concerns the aspects of: filtering current harmonics, reactive power compensation (defined in the fundamental harmonic domain), supply current balancing and dynamic performance. The results of the laboratory investigation, using the fast prototyping system dSPACE, are given in the paper. This paper confirms that the current's physical components theory allows developing the control algorithm of shunt active power filter and its practical implementation. The investigation allows the conclusion that this control algorithm enables achieving the supply system current shape close to the sinusoidal, despite shunt active power filter operation under the distorted supply voltage. A sinusoidal supply current cannot be attained by the control algorithm based on the p-q power theory without some additional control elements, such as: PLL, signal filters, etc. The experiment also has shown that the control algorithm based on the p-q power theory is easier to implement and less demanding in terms of hardware than the control algorithm based on the current's physical components theory.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2007, 13, 1; 59-66
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-5 z 5

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies