Tytuł:
Corona Modeling for the Transient Analysis, Steady State and Corona Loss Performance of Transmission Lines
Autorzy:
Saied, M. M.
Powiązania:
https://bibliotekanauki.pl/articles/262685.pdf
Data publikacji:
2013
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
corona
power transmission lines
electromagnetic modeling
computer simulation
losses
transient analysis
shunt compensation
optimization
Opis:
This paper addresses the steady state analysis and the electromagnetic transients of overhead power transmission lines exhibiting corona. After a brief survey of the currently available modeling techniques, an alternative approach to the simulation of the corona discharge is presented. It is based on adding voltage-dependent current sources at prespecified nodes within the line’s lumped, ladder-shaped, equivalent circuit including an aduqate number of sections. The characteristics of these current sources can be determined using the usually available corona power loss measurements under power frequency sinusoidal voltage conditions. The line model is used for finding its transient response using time domain techniques. Several voltage excitation waveforms and magnitudes as well as different line’s loading conditions are investigated. As a further application of the suggested approach, the minimizion of the total corona losses of a long shunt compensated line will be considered as an additional criterion in the process of identifying the appropriate rating and location of the compensating coil primarily used for improving the line’s voltage profile.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2013, 16, 2; 11-20
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Solution Methods of Overhead Transmission Line Mechanics
Autorzy:
Varga, L.
Ilenin, S.
Chladný, V.
Powiązania:
https://bibliotekanauki.pl/articles/262625.pdf
Data publikacji:
2006
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
overhead transmission lines mechanics
mechanical tension
catenaries curve
Opis:
Paper is focused to mechanics calculation of overhead transmission lines. In first part of this paper is presented mathematical model for complex solution of overhead line mechanics in a plan. Non-level overhead line can be considered. The second part of paper deals with a solution method of the mechanics of overhead line conductors in three-dimensional space in non- level span. This method enables to define three-dimensional location, vector of mechanics stress of suspended line in optional point of line under combined load caused by the ice and the wind of optional direction.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2006, 12, 1; 17-20
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Methods for Canceling the Power Frequency Magnetic and Electric Fields at Pre-Specified Points on the Lines’ Corridors
Autorzy:
Saied, M. M.
Powiązania:
https://bibliotekanauki.pl/articles/262789.pdf
Data publikacji:
2009
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
power transmission lines
magnetic field
electrostatic interference
mitigation
shielding
Opis:
Methods are presented for the cancellation of the power line’s magnetic and electric fields at pre-specified points close to the line corridor. For canceling the magnetic field, three auxiliary conductors constituting two mitigating loops are used. Their configuration should be geometrically similar to the arrangement of the 3-phase power line’s conductors, with respect to the point at which a zero magnetic field is required. A procedure is suggested for the optimal selection of the scaling factor relating the power conductors’ and the mitigating conductors’ geometrical dimensions. In a case study, the magnetic field reduction varies between 100% near the zero-field point to 35% to the right of that point, with an optimal scaling factor of 0.15. Similar procedure can be used for cance¬ling the electric field at a pre-specified point. The three auxiliary conductors should carry charges proportional to those on the active conductors, but of opposite signs. Results show that the field at the specified point will be exactly zero, instead of the original value of 2.6kV/m. The three voltages required to supply the auxiliary conductors are 76.62, 62.53 and 51.50kV, with almost equal phase angles. The fact that the potentials of the three auxiliary conductors are almost in phase suggests the possibility of using one transformer with appropriate taps to supply them.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2009, 15, 2; 13-19
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
The Transient Performance of Partially-Undergrounded Overhead Lines in the Presence of Corona
Autorzy:
Saied, Mohamed M.
Powiązania:
https://bibliotekanauki.pl/articles/262791.pdf
Data publikacji:
2019
Wydawca:
Akademia Górniczo-Hutnicza im. Stanisława Staszica w Krakowie
Tematy:
distributed parameter circuits
non-uniform lines
power transmission lines
line modeling
transients
power networks
mixed
overhead-cable lines
partial undergrounding
distributions
mathematica
Opis:
The paper presents a method for investigating the electromagnetic transients of partially under-grounded high voltage overhead transmission lines in the presence of corona. It is based on a time domain model in which the corona is simulated by distributed voltage-dependent shunt current sources. The line segments and the inserted cable section are represented by a single equivalent transmission element having location-dependent circuit parameters per unit length. The numerical solution of the resulting set of differential equations yields the distributions of the voltage, the longitudinal current and the shunt corona current (per unit length) as functions of location and time. The presented two-, three-dimensional and contour plots proved to be helpful in discussing these distributions and in identifying any eventual current and/or voltage concentrations. The developed computer code in Mathematica can handle any time waveform of the source initiating the transients, any line termination as well as any lengths of the overhead line and cable section.
Źródło:
Electrical Power Quality and Utilisation. Journal; 2019, 21, 1; 1-8
1896-4672
Pojawia się w:
Electrical Power Quality and Utilisation. Journal
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-4 z 4

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies