Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Wyszukujesz frazę "Cooling water" wg kryterium: Temat


Wyświetlanie 1-2 z 2
Tytuł:
Cooling water flow influence on power plant unit performance for various condenser configurations setup
Autorzy:
Dobkiewicz-Wieczorek, Ewa
Powiązania:
https://bibliotekanauki.pl/articles/2091367.pdf
Data publikacji:
2022
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
cooling water
power plant efficiency
cooling water flow control
CHP plant
efficiency
Opis:
This paper presents the influence of cooling water regulation on power plant net efficiency. It was examined whether, for the non-nominal low-pressure turbine load, it is justified to reduce the cooling water pump load, and how it would affect the unit net efficiency. Calculations for two types of power units were carried out: with condensing and extraction-condensing turbine. The tested condensing power plant consists of three surface condensers. The calculation included four condensers’ connections set up on the cooling water side to check how the cooling water system pressure drop affects the net unit performance. The result has confirmed that implementing serial connection decreases net efficiency when cooling water flow regulation is used, but the mixed connection should be applied when pump load is not controlled. It was proved that the cooling water flow control gives a profit for both units. Net efficiency for combined heat and power plant can be improved by 0.1–0.5 pp, the gain is remarkable below 60% of the low-pressure turbine part load. Flow control implementation in the unit with condensing turbine water control gives a similar profit just below 80% of the turbine load. Next, an influence of the additional limitations of a cooling water system (minimal total pump head, cooling tower) affecting the feasibility of implementing the water control has been considered. Applying a multi-cell forced draft cooling tower does not have a significant impact on results, but when a natural draft cooling tower is used, the flow control range is strongly reduced.
Źródło:
Archives of Thermodynamics; 2022, 43, 1; 141--167
1231-0956
2083-6023
Pojawia się w:
Archives of Thermodynamics
Dostawca treści:
Biblioteka Nauki
Artykuł
Tytuł:
Operating characteristics of transcritical CO2 heat pump for simultaneous water cooling and heating
Autorzy:
Sarkar, J.
Bhattacharyya, S.
Powiązania:
https://bibliotekanauki.pl/articles/240930.pdf
Data publikacji:
2012
Wydawca:
Polska Akademia Nauk. Czytelnia Czasopism PAN
Tematy:
charakterystyki pracy
eksperyment
pompa ciepła
symulacja
CO2 heat pump
experiment
performance characteristics
simulation
Water cooling and heating
Opis:
The effects of water-side operating conditions (mass flow rates and inlet temperatures) of both evaporator and gas cooler on the experimental as well as simulated performances (cooling and heating capacities, system coefficient of performance (COP) and water outlet temperatures) of the transcritical CO2 heat pump for simultaneous water cooling and heating the are studied and revised. Study shows that both the water mass flow rate and inlet temperature have significant effect on the system performances. Test results show that the effect of evaporator water mass flow rate on the system performances and water outlet temperatures is more pronounced (COP increases by 0.6 for 1 kg/min) compared to that of gas cooler water mass flow rate (COP increases by 0.4 for 1 kg/min) and the effect of gas cooler water inlet temperature is more significant (COP decreases by 0.48 for given range) compared to that of evaporator water inlet temperature (COP increases by 0.43 for given range). Comparisons of experimental values with simulated results show the maximum deviation of 5% for cooling capacity, 10% for heating capacity and 16% for system COP.
Źródło:
Archives of Thermodynamics; 2012, 33, 4; 23-40
1231-0956
2083-6023
Pojawia się w:
Archives of Thermodynamics
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-2 z 2

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies