Tytuł:
Influence of the converter transformer valve-side bushing fault on commutation reactance protection and improvement scheme
Autorzy:
Zhang, Yanxia
Dong, Guanghao
Wei, Le
Ma, Jinting
Du, Shanshan
Powiązania:
https://bibliotekanauki.pl/articles/27309943.pdf
Data publikacji:
2023
Wydawca:
Polska Akademia Nauk. Czasopisma i Monografie PAN
Tematy:
commutation reactance
converter transformer
improvement scheme
overcurrent protection
valve-side bushing fault
VSC HVDC system
Opis:
Commutation reactance is an important component in the voltage-source converter-based high-voltage direct current (VSC–HVDC) transmission system. Due to its connection to the converter, when there is a fault occurring on the valve-side bushing of a converter transformer, the nonlinearity operation of the converter complicates the characteristics of current flowing through commutation reactance, which may lead to maloperation of its overcurrent protection. It is of great significance to study the performance of commutation reactance overcurrent protection under this fault condition and propose corresponding improvement measures to ensure the safe and stable operation of AC and DC systems. In the VSC–HVDC system with the pseudo-bipolar structure of a three-phase two-level voltage source converter, the valve has six working periods in a power frequency cycle, and each period is divided into five working states. According to the difference between the fault phase and non-fault phase of the conductive bridge arms at the time of fault occurrence, these five working states are merged into two categories. On this basis, various faults of the valve-side bushing of a converter transformer are analyzed, and the conclusion is drawn that the asymmetric fault of valve-side bushing can lead to the maloperation of the commutation reactance overcurrent protection. Based on the characteristics that the current flowing through the commutation reactance after the asymmetric fault of the valve-side bushing contains decaying aperiodic components in addition to the fundamental frequency wave, a scheme to prevent the maloperation of commutation reactance overcurrent protection is proposed, which uses the unequal of two half cycle integral values with different starting points to realize the blocking of commutation reactance overcurrent protection, and it makes up the deficiency of existing protection in this aspect. Finally, this paper builds a VSC–HVDC system simulation model in the PSCAD/EMTDC platform to verify the effectiveness of the scheme.
Źródło:
Archives of Electrical Engineering; 2023, 72, 3; 715--735
1427-4221
2300-2506
Pojawia się w:
Archives of Electrical Engineering
Dostawca treści:
Biblioteka Nauki
Artykuł
    Wyświetlanie 1-1 z 1

    Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies