The diagnostics of power transformers is a very fast developing branch, due to increasing average age of assets and changes in asset management strategies, nowadays companies introduce asset management based on a real technical condition. One of important methods used for diagnostics of a transformer’s active part is Frequency Response Analysis (FRA). It allows determination of mechanical condition of windings, their displacements, deformations and electric faults, as well as some problems with internal leads and connections, core and bushings. For the aim of windings impedance modeling the RLC models are applied. The idea of lumped parameters models was presented in [6]. The new universal model basing on circuit solution is developed in this paper. Lumped parameters used in calculations are obtained with finite element method and Maxwell package. The examples of models created for simple windings were compared to real measurements.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies