The diagnostics of power transformers is a very fast developing branch. Due to increasing average age of assets and changes in asset management strategies, nowadays companies introduce asset management based on technical condition. One of important methods used for diagnostics of a transformer’s active part is Frequency Response Analysis (FRA). It allows determination of mechanical condition of windings, their displacements, deformations and electric faults, as well as some problems with internal leads and connections, core and bushings. In the FRA measurements of many power transformers there can be observed a first resonance, which position on frequency axis and damping factor seems to be similar for primary and secondary windings. The authors are going to explain this strange phenomenon, not depending on inductance of the winding being measured.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies