Passive filters are widely used to mitigate the effect of load harmonics on the supply
power grid. Topology selection of the filters is based on the frequency bandwidth to be
suppressed. Filter topologies comprising single-tuned filters and damped filters are the
most popular in industrial power system applications. The article focuses on the influence
of the damped C-type 2nd harmonic filter on the transients behavior under arc transformer
energization in the arc furnace power supply system compensated by SVC. The
examination results of transient currents and voltages across capacitors and reactors of
the 3rd and 5th passive filters are compared for two topologies of the SVC filter circuits:
with and without C-type filter. The Matlab/Simulink Software was used to modeling
filter behavior during unload transformer switching-on.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies