In providing clean water services to a community, a clean water supply distribution network system is very important. This study is aimed at the determination of the distribution pipe network by simulating and optimizing the water supply system in the Arjawinangun area, Cirebon, West Java, Indonesia. The data collected was analyzed by using EPANET 2.0 software for modelling water distribution systems. The results show that the total domestic and non-domestic water demand is 391.41 l/s, with a leakage rate of 20%. The pipeline installation plan for the Arjawinangun area is planned to be installed for a length of 23,045 m, with pipe diameters ranging from 400 to 90 mm. The Arjawinangun Area Offtake Reservoir drainage system, which is at an elevation of +25 m above sea level, requires a distribution pump with a head (H) of 6.0 bar. Also, using the gravity distribution technique, a water tower can be built (~ 55 m) as a water supply booster pump.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies