Zjawisko występowania drgań ferrorezonansowych w systemie elektroenergetycznym jest istotnym problemem w elektroenergetyce. W artykule przedstawiono badania symulacyjne możliwości wystąpienia ferrorezonansu w sieci 110 kV.
The ferroresonance phenomena in the power system is a significant problem in electric grid. The nonlinear vibration of the current and the voltage present a risk to the electrical apparatus. Due to the nonlinearity of that phenomena a classical analysis method are not applicable and digital methods of analysis are necessary. The article present a risk to the electrical apparatus. Due to the nonlinearity of that phenomena a classical analysis method are not applicable and digital methods of analysis are necessary. The article presents application of the EMTP-ATP program to determine simulation results. EMTP-ATP is a universal program system for digital simulation of transient phenomenon of electromagnetic. To analysis was subjected the 110kV double-circuit overhead lines with two different nonlinear elements – power transformer and voltage transformer. That types of circuit is one of the susceptible to ferroresonance oscillations. Computer simulations confirmed that theory. The oscillation were observed for the given configuration. The results of the simulation shows that a voltage transformer are particularly vulnerable to ferroresonance phenomenon.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies
Informacja
SZANOWNI CZYTELNICY!
UPRZEJMIE INFORMUJEMY, ŻE BIBLIOTEKA FUNKCJONUJE W NASTĘPUJĄCYCH GODZINACH:
Wypożyczalnia i Czytelnia Główna: poniedziałek – piątek od 9.00 do 19.00