Providing roughness is an effective method to heat fluids to
high temperature. Present paper make use of concave dimple roughness on
one and three sides of roughened ducts aimed at determining rise in heat
transfer and friction of three sides over one side roughened duct. Three sides
roughened duct produces high heat transfer compared to one side roughened.
Results are shown as a rise in Nusselt number and friction factor of three
sides over one side roughened duct. Experimental investigation was conducted under actual outdoor condition at National Institute of Technology
Jamshedpur, India to test various sets of roughened collectors. Roughness
parameter varied as relative roughness pitch 8–15, relative roughness height
0.018–0.045, dimple depth to diameter ratio 1–2, Reynolds number 2500–
13500 at fixed aspect ratio (width/hight) 8. Highest enhancement in Nusselt
number for varying relative roughness pitch, height, and diameter ratio was
respectively found as 2.6 to 3.55 times, 1.91 to 3.42 times and 3.09 to 3.94
times compared to one side dimple roughened duct. Highest rise in friction
for three sides over one side roughened duct for these varying parameters
was respectively found as 1.62 to 2.79 times, 1.52 to 2.34 times and 2.21 to
2.56 times. To visualize the effect of roughness parameter on heat transfer and friction factor, variation in Nusselt number and friction factor for
varying roughness parameters with Reynolds number is shown.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies