This paper presents an analysis of the properties of pulse width modulator with a single (symmetrical regular sampled PWM) and double (asymmetrical regular sampled PWM) control sampling of the input signal (low-frequency control input wave) in presence of a triangular auxiliary signal. In this paper, a comparison of the characteristics of these modulators used in the control system with a linear proportional controller is presented. The article provides the relations derived for the maximum amplification of regulators for which the control system operates stably. Analysis results have been confirmed by simulation and experimental studies of a commercial active filter installed in an industrial plant.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies