Accurate fault location in an electric power distribution system (EPDS) is important
in maintaining system reliability. Diverse methods have been proposed in the
past. These methods whither require measurements at each load point or use single-step
loads compensation, which is hardly available in practical uses. In this paper, a simple
technique to bypass the load problems is proposed. The method requires calculating an
optimal load distribution using the total load seen from the substation (The rated power
of distribution transformers) and the network topology. The optimal load distribution is
used as a fictive distribution to replace the real unknown one in fault location (FL) algorithms.
The effectiveness of the proposed technique is demonstrated using a mathematical
formulation first, and next, by several simulations with a classic iterative fault location
algorithm. The test results are obtained from the numerical simulation using the data
of a distribution line recognized in the literature.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies