This paper presents a novel approach for reactive power planning of a connected
power network. Reactive power planning is nothing but the optimal usage of all
reactive power sources i.e., transformer tap setting arrangements, reactive generations of
generators and shunt VAR compensators installed at weak nodes. Shunt VAR compensator
placement positions are determined by a FVSI (Fast Voltage Stability Index) method.
Optimal setting of all reactive power reserves are determined by a GA (genetic
algorithm) based optimization method. The effectiveness of the detection of the weak
nodes by the FVSI method is validated by comparing the result with two other wellknown
methods of weak node detection like Modal analysis and the L-index method.
Finally, FVSI based allocation of VAR sources emerges as the most suitable method for
reactive power planning.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies