This paper presents the implementation of a thermal camera for the quantitative
estimation of power losses in a high frequency planar transformer (100 kHz/
5600 VA). The methodology is based on the observation of the transient temperature rise
and determination of the power losses by means of curves representing the derivative of
temperature as a function of power losses dissipated in the transformer. First, the thermal
calibration characteristics had to be obtained from a simple experiment, where power
losses are generated by DC current in the ferrite core and windings. Next, experimental
investigations focused on the determination of the transformer power losses for a short
circuit and no load, with a resistive load and with the rectifier as a load were carried out.
Finally, to verify the obtained results, analytical calculations based on Dowell’s and modified
Steinmetz’s equations were additionally made, which showed a good convergence.
The proposed method is easy to implement and can be used as an alternative to the calorimetric
method which is time-consuming and requires a complicated measurement
setup.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies