Long transmission lines have to be compensated to enhance the transport of active power. But a wrong design of the compensation may lead to subsynchronous resonances (SSR). For studies often park equivalent circuits are used. The parameters of the models are often determined analytically or by a three-phase short-circuit test. Models with this parameters give good results for frequencies of 50 Hz and 100 Hz resp. 60 Hz and 120 Hz. But SSR occurs at lower frequencies what arises the question of the reliability of the used models. Therefore in this publication a novel method for the determination of Park equivalent circuit parameters is presented. Herein the parameters are determined form time functions of the currents and the electromagnetic moment of the machine calculated by transient finite-element simulations. This parameters are used for network simulations and compared with the finite-element calculations. Compared to the parameters derived by a three-phase short-circuit a significant better accuracy of simulation results can be achieved by the presented method.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies