Arresters are widely used in power systems to protect other equipment against
overvoltages. However, in some conditions, they can’t operate successfully. One of the
disturbances leading to the failure of the riser pole arresters is the ferroresonance overvoltages.
In this paper, at first the influence of different transformer simulation models of
ATP software on the occurrence of ferroresonance is studied and then the effect of ferroresonance
on the riser pole arrester has been scrutinized through the thermal and electrical
performance of the arrester in an underground distribution system. The results
show that the arrester temperature rises due to energy dissipation in a ferroresonance
circumstance, which indeed may result into the explosion of the arrester. Also, applying
different models of the transformer in the ATP software and comparing the results, it is
shown that the available models do not show the same effect on the arrester.
Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies